6201-WA-DFNT to DFNT ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Setup Guide August 12, 2008
Please Read This Notice Successful application of this module requires a reasonable working knowledge of the ProLinx Module, its connected devices, and the application in which the combination is to be used. For this reason, it is important that those responsible for implementation satisfy themselves that the combination will meet the needs of the application without exposing personnel or equipment to unsafe or inappropriate working conditions. This manual is provided to assist the user.
Contents 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Contents Please Read This Notice 2 Important Installation Instructions ....................................................................................................... 2 Your Feedback Please........................................................................................................................ 2 1 Introduction 1.1 1.2 1.3 2 Before You Begin .........................................................
Contents Page 4 of 45 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway ProSoft Technology, Inc.
Introduction 1 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Introduction In This Chapter Before You Begin .................................................................................... 5 Using the Sample ProSoft Configuration Builder Files ............................ 6 About Transmission Casts.......................................................................
201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 1.2 Introduction Using the Sample ProSoft Configuration Builder Files The sample application uses two 6201-WA-DFNT modules to establish wireless communications between a ControlLogix PLC at a main site and a ControlLogix PLC located at a remote site. Both DFNT modules are configured as Clients. The following diagram illustrates this application.
Introduction 1.3 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway About Transmission Casts The sample uses a UNICAST transmission type. UNICAST means that you set up Produce and Consume Commands that transfer or receive data between two individual modules. For example, a Produce command can specify that this data is only produced to one particular consuming module based on the consuming modules IP address.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Page 8 of 45 Introduction ProSoft Technology, Inc.
Load the Required Software 2 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Load the Required Software In This Chapter Install ProSoft Configuration Builder (PCB) ............................................. 9 Copy the Sample Application File..........................................................
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 2.2 Load the Required Software Copy the Sample Application File 1 2 3 From the ProLinx Solutions splash screen, click Documentation. Choose Samples → Wireless. Product Copy the PROLINX WIRELESS SAMPLE.PPF file to a location on your PC or Laptop. Page 10 of 45 ProSoft Technology, Inc.
Configure the 6201-WA-DFNT 150 Module 3 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Configure the 6201-WA-DFNT 150 Module In This Chapter Complete the ProSoft Configuration Builder Sections ........................... 12 Save and Download the Configuration File to the 6201-WA-DFNT Client 150 ........................................................................................................
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 3.1 Configure the 6201-WA-DFNT 150 Module Complete the ProSoft Configuration Builder Sections 3.1.1 Radio Ethernet Configuration 1 Double-click the icon. Every EtherNet/IP module is set up with the defaults shown in the example. You may have to modify values such as the Radio Default Gateway, the Network Name (SSID), and the Station Name to suit the needs of your network.
Configure the 6201-WA-DFNT 150 Module 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 3.1.2 Radio Configuration (Client_150) Expand the Wireless Configuration section and double-click on the icon. The default Signal LED 1 through 4 parameter values are fixed and cannot be modified. If you need to change the values for the remaining parameters in this dialog box, make sure to save your changes before moving on to the next step.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Configure the 6201-WA-DFNT 150 Module Transmit Rate This parameter defines the data rate(s) for transmission of directed messages. Possible values are outlined in the following table. Value Definition 1 Fixed 1 Mbit (1) 2 Fixed 2 Mbit (2) 3 Auto fallback high (11, 5.5, 2, 1) 4 Fixed medium rate (5.5) 5 Fixed high rate (11) 6 Auto fallback standard (2, 1) 7 Auto fallback medium (5.
Configure the 6201-WA-DFNT 150 Module 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway This section is used to synchronize the time using a centralized atomic clock. This feature is only usable if your modules are communicating through an access point such as a RadioLinx Industrial Hotspot. The values in this window should be left with the default values. As you select each parameter, the help window on the screen displays information to help you make your selections.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Configure the 6201-WA-DFNT 150 Module Producer Command Narrative for the First Command: The first Produce command (on line 3) is as follows. 1 2 3 4 5 6 Send data using Unicast Mode Send the data to IP Address 172.16.10.151. Send 600 registers beginning at DB Register 1200. Do not set a Swap Code. Send the data every 100 milliseconds (producer commands must be 1/4 of consumer commands). Use an Exchange ID of 1002.
Configure the 6201-WA-DFNT 150 Module 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway The corresponding Consume command on the DFNT Client 151 looks like this: This command states: Receive 600 words of data with each exchange ID = 1002 from IP: 172.16.10.150 and place them in 600 registers beginning at database register 1200. Receive data within 400 ms using UNICAST. The second Consume command is set up the same way.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Configure the 6201-WA-DFNT 150 Module 3 Click the Edit button. The Edit window appears. 4 Define each element of the command by selecting the element, then select or enter the desired values. Click OK when done. 5 Note: In addition to the help on the dialog, the PWP Driver Manual located on the ProLinx Solutions CD provides descriptions of each parameter.
Configure the 6201-WA-DFNT 150 Module 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 3.1.5 Radio PWP Multicast Group List This section does not contain any data for the sample application. The sample application uses UNICAST transmission and therefore there is no need to enter IPs of other devices in this section. The ProLinx PWP Driver Manual describes this section in detail. 3.1.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Configure the 6201-WA-DFNT 150 Module 3.1.7 DFNT Client 0 Commands Double-click on the icon. Note: For command lines 1 and 2 to function properly with the ControlLogix processor, the menu item "Logic/Map PLC/SLC Messages ..." in the RSLogix 5000 application, must have the "File Number" field in the "PLC 2, 3, 5 / SLC Mapping" dialog box linked / associated with a user specified "Tag Name" Field Tag.
Configure the 6201-WA-DFNT 150 Module 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 3.1.8 CommonNet Expand the CommonNet section. Double-click on the icon. This section does not require any editing for the sample application. Refer to the DFNT Driver Manual located on the ProLinx Solutions CD for information on setting up data mapping for your application. Double-click on the icon. This section does not require any editing for the sample application.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 3.2 Configure the 6201-WA-DFNT 150 Module Save and Download the Configuration File to the 6201-WA-DFNT Client 150 1 2 Ensure that your PC or Laptop is still connected to the DEBUG port of the 6201-WA-DFNT Client 150 module. Apply power to the module if you have not already done so. Choose File → Save As… and save the .PPF file to a location on your hard drive.
Configure the DFNT Client 151 Module 4 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Configure the DFNT Client 151 Module In This Chapter Complete the ProSoft Configuration Builder Sections ........................... 23 Save and Download the Configuration File to the 6201-WA-DFNT Client 151 ........................................................................................................
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Configure the DFNT Client 151 Module In the sample application, this radio's IP address is set to 172.16.10.91. In our sample application, the 6202-WA-DFNT-DFCM3 Primary Client IP address is set to 172.16.10.91, so here we used the next IP address in the range which happens to be 90. When you build your own application, you will have to modify the Radio Default Gateway, Network Name (SSID), and Station Name to suit your needs.
Configure the DFNT Client 151 Module 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Transmit Rate This parameter defines the data rate(s) for transmission of directed messages. Possible values are outlined in the following table. Value Definition 1 Fixed 1 Mbit (1) 2 Fixed 2 Mbit (2) 3 Auto fallback high (11, 5.5, 2, 1) 4 Fixed medium rate (5.5) 5 Fixed high rate (11) 6 Auto fallback standard (2, 1) 7 Auto fallback medium (5.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Configure the DFNT Client 151 Module This section is used to synchronize the time using a centralized atomic clock. This feature is only usable if your modules are communicating through an access point such as a RadioLinx Industrial Hotspot. The values in this window should be left with the default values. As you select each parameter, the help window on the screen displays information to help you make your selections.
Configure the DFNT Client 151 Module 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway The first Produce command (on line 1) is as follows. 1 2 3 4 5 6 7 Send data using Unicast Mode Send the data to IP Address 172.16.10.150. Send 600 registers beginning at DB Register 0. Do not set a Swap Code. Send the data every 100 milliseconds (producer commands must be 1/4 of consumer commands). Use an Exchange ID of 1000.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Configure the DFNT Client 151 Module This command states: Receive 600 words of data with each exchange ID = 1002 from IP: 172.16.10.150 and place them in 600 registers beginning at database register 1200. Receive data within 400 ms using UNICAST. The second Consume command is set up the same way. It must correspond to the second Produce command in order to accept the data coming from it.
Configure the DFNT Client 151 Module 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 4.1.5 Radio PWP Multicast Group List This section does not contain any data for the sample application. The sample application uses UNICAST transmission and therefore there is no need to enter IPs of other devices in this section. The ProLinx PWP Driver Manual describes this section in detail. 4.1.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Configure the DFNT Client 151 Module 4.1.7 DFNT Client 0 Commands Double-click on the icon. Note: For command lines 1 and 2 to function properly with the ControlLogix processor, the menu item "Logic/Map PLC/SLC Messages ..." in the RSLogix 5000 application, must have the "File Number" field in the "PLC 2, 3, 5 / SLC Mapping" dialog box linked / associated with a user specified "Tag Name" Field Tag.
Configure the DFNT Client 151 Module 4.2 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Save and Download the Configuration File to the 6201-WA-DFNT Client 151 1 Connect your PC or Laptop to the DEBUG port of the 6201-WA-DFNT Client 151 module. Apply power to the module if you have not already done so. 2 Choose File → Save As… and save the .PPF file to a location on your hard drive. 3 Right-click on 6201-WA-DFNT_151 and select Download from PC to Device.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 4 Configure the DFNT Client 151 Module Select the appropriate COM port and click the Download button. The download is complete when the OK button becomes active. When the download is complete, click OK. Note: Once the configuration is downloaded to the module, the Port 0 Err LED may be flashing. This is common behavior since an Ethernet/IP device is not directly connected to the DFNT Client 151.
Verify Data Exchange 5 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Verify Data Exchange Run Diagnostics Using ProSoft Configuration Builder 1 Move the connector from the Debug Port on the DFNT Client 151 module and plug it into the Debug Port of the DFNT Client 150 module. Ensure that power is applied to both modules. 2 Right-click on 6201 WA-DFNT_150 and select Diagnostics. 3 Select the appropriate Com port ProSoft Technology, Inc.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 4 5 6 7 Verify Data Exchange Press "?" to display the Diagnostic menu. Press "D" to display the Database menu. Press "3" to show database registers beginning at 3000. Press the "S" key to refresh the database values. The circled values in the example should change each time you press the "S" key indicating that data is being passed between modules. If these values do not change, contact ProSoft Technical Support.
Default Module Configuration Assignments 6 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Default Module Configuration Assignments In This Chapter 6.1 IP Addresses ......................................................................................... 35 WATTCP Parameters............................................................................ 35 IP Addresses IP Address are assigned in ranges to each of the WA modules.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Page 36 of 45 Default Module Configuration Assignments ProSoft Technology, Inc.
Support, Service & Warranty 7 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Support, Service & Warranty In This Chapter How to Contact Us: Technical Support.................................................. 37 Return Material Authorization (RMA) Policies and Conditions............... 38 LIMITED WARRANTY........................................................................... 40 ProSoft Technology, Inc.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Support, Service & Warranty North America/Latin America (excluding Brasil) (location in California) +1.661.716.5100, support@prosoft-technology.com (mailto:support@prosofttechnology.
Support, Service & Warranty 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 7.2.2 Procedures for Return of Units Under Warranty: A Technical Support Engineer must approve the return of Product under ProSoft's Warranty: a) A replacement module will be shipped and invoiced. A purchase order will be required. b) Credit for a product under warranty will be issued upon receipt of authorized product by ProSoft at designated location referenced on the Return Material Authorization.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 7.3 Support, Service & Warranty LIMITED WARRANTY This Limited Warranty ("Warranty") governs all sales of hardware, software and other products (collectively, "Product") manufactured and/or offered for sale by ProSoft, and all related services provided by ProSoft, including maintenance, repair, warranty exchange, and service programs (collectively, "Services").
Support, Service & Warranty 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway b) This Warranty does not cover the failure of the Product to perform specified functions, or any other non-conformance, defects, losses or damages caused by or attributable to any of the following: (i) shipping; (ii) improper installation or other failure of Customer to adhere to ProSoft's specifications or instructions; (iii) unauthorized repair or maintenance; (iv) attachments, equipment, options, parts,
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Support, Service & Warranty a) Any documentation included with Product purchased from ProSoft is protected by copyright and may not be duplicated or reproduced in any form without prior written consent from ProSoft. b) ProSoft's technical specifications and documentation that are included with the Product are subject to editing and modification without notice.
Support, Service & Warranty 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway 7.3.7 Time Limit for Bringing Suit Any action for breach of warranty must be commenced within 39 months following shipment of the Product. 7.3.
6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Page 44 of 45 Support, Service & Warranty ProSoft Technology, Inc.
Index 6201-WA-DFNT ♦ ProLinx Wireless High Speed Wireless EtherNet/IP Gateway Produce and Consume Commands • 18, 28 Purchasing Warranty Extension: • 39 R Index A About Transmission Casts • 7 All Product Returns: • 38 Allocation of Risks • 43 B Radio Configuration • 24 Radio Configuration (Client_150) • 13 Radio Ethernet Configuration • 12, 23 Radio PWP Exchanges (Client_150) • 15 Radio PWP Exchanges (Client_151) • 26 Radio PWP Multicast Group List • 19, 29 Radio SNTP Client • 14, 25 Return Material Aut