Setup guide
Configure the ASCII Module 6201-WA-DFNT ♦ ProLinx Wireless
High Speed Wireless ASCII Generic Serial Gateway
ProSoft Technology, Inc. Page 13 of 50
September 6, 2007
3 Configure the ASCII Module
In This Chapter
¾ Complete the ProSoft Configuration Builder Sections............ 14
¾ Save and Download the Configuration File to the 6201-WA-ASCII
............................................................................................... 21
Based on the sample application, the remote Server is connected to a 6201-WA-
DFNT configured as a Client. The goal here is to begin to establish
communications between the 6201-WA-ASCII and the 6201-WA-DFNT
modules. The default configuration is designed to pass 1200 words between
each module. Each module is configured separately.
Configuration is accomplished using ProSoft Configuration Builder (PCB). The
default configuration file is PROLINX WIRELESS SAMPLE.PPF.
1 Start PCB.
2 Select File → Open.
3 Navigate to the location where you copied the PROLINX WIRELESS
SAMPLE.PPF file and select this file.
4 Expand the ASCII Serial to EtherNetIP folder.
5 Expand the 6201-WA-ASCII module selection.