PROTECTION 
  Protection  Conditions Status
  PV Reverse Polarity  When the battery is correct connecting, the  The controller is not 
  PV can be reversed.  damaged
  Battery Reverse Polarity  When the PV is not connecting, the battery  Stop charging 
  can be reversed.
  Battery Over Voltage  The battery voltage reaches to the OVD  Stop discharging
  Battery Over Discharge  The battery voltage reaches to the LVD
  Battery Overheating  Temperature sensor is higher than 65
o
  Output is OFF 
  Temperature sensor is less than 55
o
Output is ON
  Controller Overheating  Temperature sensor is higher than 85
o
  Output is OFF 
  Temperature sensor is less than 75
o
  Output is ON
  Load Short Circuit  Load current ≥2.5 times rated current  Output is OFF 
  One short circuit, the output is OFF 5s;  Clear the fault: 
  Two short circuit, the output is OFF 10s;  Restart the controller 
  Three short circuit, the output is OFF 15s;  or wait for one 
  Four short circuit, the output is OFF 20s;  night-day cycle 
  Five short circuit, the output is OFF 25s;  (night time>3 hours) 
  Six short circuit, the output is OFF
  Load Overload  Load current ≥2.5 times rated current  Output is OFF 
  1.02-1.05 times, 50s,  Clear the fault: 
  1.05-1.25 times, 30s  Restart the controller 
  1.25-1.35 times,10s  or wait for one 
  1.35-1.5 times 2s  night-day cycle 
    (night time>3 hours)
  Damaged RTS (Temp. Sensor)  The RTS is short-circuited or damaged  Charging or 
    discharging at 25
o