Installation Guide

Electrical Connections
1. Verify the power is off before installation
2. Connect the ground (Green) lead to suitable ground.
3. Connect fixture neutral (White) lead to supply neutral (White) lead.
4. Connect hot lead (Orange) to supply hot lead, 100 to 300 volts.
5. Connect switch (Red) wire as required for operating fixture. As Required:
a) Normally ON Connect Red wire to Orange wire for fixture to be on in AC and emergency modes (see Fig. 4).
b) Normally OFF Do not connect Red wire, cap off. Unit will only come on during emergency mode (see Fig. 5).
c) Switched Connect Red wire to switch leg of the device that will be controlling the fixture. Unit can be switched
on and off. Unit will come on in emergency mode no matter what position the switch device is in (see Fig. 6).