OPERATION
“AC ON” LED is illuminated when AC power is present. 
NOTE: All models are supplied with an AC Lockout circuit, which prevents the emergency lights from illuminating  
   when the battery is connected and no AC power is present. 
NOTE: All models are supplied with a Low Voltage Disconnect circuit, which prevents damage to the battery from 
   deep discharge during prolonged emergency operation.
NOTE: Batteries are often shipped in a discharged state – this is normal. The battery will require charging. Allow 
   24 hours of charging before testing the unit. 
Models with Self-Testing/Self-Diagnostic Circuitry 
Models equipped with the self-testing/self-diagnostic electronics system provide: 
 Visual indication of AC power status   Visual indication of self-diagnostic test status and results 
-- Visual indication of any unit malfunctions include – 
 Battery Disconnected   Battery Fault   Charger Fault   LED Driver Fault   Lamp Fault 
Self-Diagnostic equipped units also include: 
Brownout protection: unit will automatically transfer to emergency operation upon detection of low AC power (approximately 80% of 
nominal line). 
Time Delay Retransfer: upon return of normal AC power, unit will remain in emergency mode for an additional 15 minutes to allow AC 
power to stabilize. 
LED Status Indicator 
A bicolor LED (green/red) is p
rovided on the control panel 
of all models equipped with the Self-Diagnostic option. 
Green Operating Status LED: 
The green Operating Status LED serves as both an AC
power and self-test indicator. During normal operation, 
the green Operating Status LED will be illuminated,
indicating the presence of AC power. During all auto- 
matic or manual self-test cycles, the green Operating 
Status LED will blink twi
ce every second. 
Red Service Alert LED: 
Under normal operating conditions, the red Service Alert 
LED indicator will remain off. If the Self-Diagnostic co
ntroller 
detects a malfunction, the red Service Alert LED will blink 
in the pattern listed in the following table: 
Automatic Tests        
The unit will automatically initiate a self-test/self-diagnostic 
cycle based on the following table: 
Testing Period  Duration of Test 
Once a month  1 minute 
Once every 6 
  months 
Alternating: 
30 minutes or 60 minutes 
Manual Tests                
Using the unit test switch, users can initiate different 
duration test cycles based on the following table: 
Initiating Action  Test Cycle 
Press test switch once  1 minute 
Press test switch twice  90 minutes 
Pressing the test switch any time after a 90 min. test 
cycle has begun cancels the remainder of the 90 min. test 
and returns the unit to normal operation. 
 Red Status LED Code   Description 
 One blink ON/pause   Battery disconnected 
 Two blinks ON/pause   Battery fault 
 Three blinks ON/pause   Charger fault 
 Four blinks ON/pause   LED Driver fault 
 Five blinks ON/pause   Lamp fault 
Red/Green alternating    Load Learn in Process 
OPERATION
4