Installation Guide
Page 2
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the
I-42-EM-A unit connector is disconnected.
1. LAMPS OPERATED
Refer to the chart below for the type of lamp(s) operated and the number of lamps to be operated in the
emergency mode.
If you have any questions regarding specific lamps, contact customer service.
Illustration 1
Downlight Fixture
INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.
FLEX “A”
JUNCTION
BOX
CEILING
TILE
A.C. BALLAST &
LAMP SOCKET COMPARTMENT
FLEX “B”
SWITCH BOX
TEST SWITCH
CHARGE LIGHT
The 6″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads discon-
nected and capped.
2. MOUNTING THE I-42-EM-A
When used with ceiling mounted downlight fixtures, the I-42-EM-A should be mounted on the fixture above the
ceiling. The flex conduit marked “A” should be wired into the ballast/lamp compartment or to an electrical junction
box on the fixture which allows access to the ballast/lamp connections. Refer to
Illustration 1
for typical mounting.
When battery packs are remote mounted, the remote distance can not exceed ½ of the distance from ballast to
lamp specified by the A.C. ballast manufacturer. For example, if the A.C. ballast manufacturer recommends no
more than 25′ remote distance, then the battery pack should not exceed 12½′. Under no circumstances should
the battery pack exceed a distance of 50′ from the lamp.