(P8066-09) Specification Sheet
P83 with P8066-28
Report No. 98029
No. Lamps: 1 Type Lamp: 13W QUAD CF-GE Total Lumens: 860
Fixture Efficiency: 55.1%
S/MH Ratio: 1.4
Single Fixture Data
Ceiling
Ht.(Ft.)
10% Values
Ft.-C Beam Dia.
Zero
Degrees
Ft.-C
50% Values
Ft.-C Beam Dia.
Ft.-C (Footcandles) are initial and measured 2'-6" from floor
16  0.1  38 0.9  0.5  19
14  0.1  32 1.3  0.7  16
12  0.2  27 1.9  1.0  13
10  0.3  21 3.1  1.5  10
8  0.6  16 5.7  2.8  8
Beam Angle - 109 Beam Angle - 69
Quick Calculator Charts
0 100 200 300 400 500
0
4
8
12
16
20
Initial Footcandles
2'6" from floor
Area per Fixture (sq. ft.)
Room Reflectances: 80% Ceiling, 50% Wall, 20% Floor
Ceiling Ht.= 9 ft.
Medium Room - RCR=5.0
120 to 200 square foot area
0 100 200 300 400 500
0
4
8
12
16
20
Initial Footcandles
2'6" from floor
Area per Fixture (sq. ft.)
Room Reflectances: 80% Ceiling, 50% Wall, 20% Floor
Ceiling Ht.= 10 ft.
Large Room - RCR=2.0
1500 to 2500 square foot area
5
15
25
35
45
55
65
75
85
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
DISTRIBUTION CURVE INTENSITY DATA
172
172
167
161
156
154
156
155
147
131
110
87
65
45
28
16
9
3
0
70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
80 70 50 30 10 0
RW
RC
10
9
8
7
6
5
4
3
2
1
0
Effective Floor Cavity Reflectance 0.20
ZONAL CAVITY COEFFICIENTS OF UTILIZATION
 66 66  66 66  64 64  64 64  61 61  61 59  59 59  56 56  56 55
 61 58  56 54  59 57  55 53  55 53  52 53  51 50  51 50  49 48
 56 51  48 45  54 50  47 44  48 46  43 47  44 42  45 43  42 40
 51 45  41 38  50 45  41 37  43 40  37 41  39 36  40 38  36 34
 47 40  36 32  45 40  35 32  38 35  32 37  34 31  36 33  31 30
 43 36  31 28  42 35  31 28  34 30  27 33  30 27  32 29  27 26
 40 32  28 24  39 32  27 24  31 27  24 30  26 24  29 26  24 22
 37 29  25 21  36 29  24 21  28 24  21 27  24 21  27 23  21 20
 34 27  22 19  33 26  22 19  26 22  19 25  21 19  24 21  19 18
 32 25  20 17  31 24  20 17  24 20  17 23  19 17  22 19  17 16
 30 23  18 15  29 22  18 15  22 18  15 21  18 15  21 18  15 14