Specifications
JAROL Assumes the promotion of energy-saving technology as its own task!
87
Function
Function
Function
Function
code
code
code
code
Name
Name
Name
Name Setting
Setting
Setting
Setting range
range
range
range
F8.20
Preset running
time
0~65535h
【 65535h 】
P re-set running time of the inverter.
When the accumulative running time achieves the
set time, the multi-function digital output terminals
will output the signal of “ running time arrival ” .
Function
Function
Function
Function
code
code
code
code
Name
Name
Name
Name Setting
Setting
Setting
Setting range
range
range
range
F8.21
FDT level
0.00~F0.0 3
【 50.00Hz 】
F8.22
FDT lag
0.0~100.0
【 5.0% 】
W hen the output frequency reaches a certain
preset frequency (FDT level), output terminal will
output an ON-OFF signal until output frequency
drops below a certain frequency of FDT level
(FDT level - FDT lag), as shown in following
figure.
Figure 6-1 9 FDT l evel and lag diagram.
Function
Function
Function
Function
code
code
code
code
Name
Name
Name
Name Setting
Setting
Setting
Setting range
range
range
range
F8.23
Frequency
arrive
detecting
range
0.0~100.0%
【 0.0% 】
When output frequency is within the detecting
range of reference frequency, an ON-OFF signal
will be output. The function can adjust the
detecting range.