Specifications

JAROL Assumes the promotion of energy-saving technology as its own task!
77
Function
Function
Function
Function
code
code
code
code
Name
Name
Name
Name Setting
Setting
Setting
Setting range
range
range
range
output
F6.09 AO1 upper limit
0.0~100.0%
100.0%
F6.10
AO1 upper limit
corresponding
output
0.00~10.00V
10.00V
These parameters determine the relationship
between analog output voltage/current and the
corresponding output value. When the analog
output value exceeds the range between lower
limit and upper limit, it will output the upper limit or
lower limit.
When AO 1 is current output, 1mA is
corresponding to 0.5V.
For different applications, the corresponding value
of 100.0% analog output is different. For details,
please refer to description of each application.
Figure 6.1 4 Relationship between AO and
corresponding setting.
Function
Function
Function
Function
code
code
code
code
Name
Name
Name
Name Setting
Setting
Setting
Setting range
range
range
range
F6. 11
AO 2 lower limit
0.0~100.0 %
0.0%
F6.12
AO2 l ower limit
corresponding
output
0~10.00V
0.00V
F6.13
AO 2 u pper limit
0.0~100.0 %
100.0%
F6.14
AO2 u pper limit
corresponding
output
0.00~10.00V
10.00V
F6.15
HDO l ower limit
0.0~100.0 %
0.0%
F6.16
HDO l ower limit
0.00 ~ 50.00kHz