Specifications

JAROL Assumes the promotion of energy-saving technology as its own task!
75
F6.01
HDO ON-OFF
output
selection
0~2 0 1
F6.02
Relay 1 output
selection
0~2 0 4
F6.03
Relay 2 output
selection
(4.0kW and
above)
0~2 0 0
OC/Relay output functions are indicated in
the following table
0 No output .
1 Running ON: Run command is ON or voltage
is being output.
2 Run forward ON: During forward run.
3 Run reverse ON: During reverse run.
4 Fault output ON: Inverter is in fault status.
5 FDT reached Please refer to description of
F8.21, F8.22.
6 Frequency reached Please refer to description
of F8.23.
7 Zero speed running ON: The running frequency
of inverter and setting frequency are zero.
8 Preset count value reached Please refer to
description of F8.18.
9 Specified count value reached Please refer to
description of F8.19.
10 overload pre-warming of inverter Please refer
to description of Fb.04~Fb.06
11 Simple PLC step completed
After simple PLC completes one step, inverter
will output ON signal for 500ms.
12 PLC cycle completed fter simple PLC
completes one cycle, inverter will output ON signal
for 500ms.
13 Running time reached ON: The accumulated
running time of inverter reaches the value of
F8.20.
14 Upper frequency limit reached ON:
Running frequency reaches the value of F0.04.
15 Lower frequency limit reached ON:
Running frequency reaches the value of F0.05.
16 Ready ON: Inverter is ready (no fault,
power is ON).
17~20 Reserved
Function
Function
Function
Function Name
Name
Name
Name Setting
Setting
Setting
Setting range
range
range
range