71
pause.
25 Pause PID
PID adjustment will be paused and inverter
keeps output frequency unchanged.
26 Pause traverse operation
Inverter keeps output frequency unchanged.
If this terminal is disabled, inverter will continue
traverse operation with current frequency.
27 Reset traverse operation
Reference frequency of inverter will be forced
as center frequency of traverse operation.
28 Reset counter
Clear the value of counter.
29 Forbid torque control mode
Torque control is forbided and switch inverter
to run in speed control mode.
30 Forbid the function of ACC/DEC
ACC/DEC is invalid and maintains output
frequency if it is enabled.
31 Counter input
The pulse input terminal of internal counter.
Maximum pulse frequency: 200Hz.
32 UP/DOWN invalid temporarily
UP/DOWN setting is invalid but will not be
cleared. When this terminal is disabled,
UP/DOWN value before will be valid again.
33~39 Reserved
Function
Function
Function
Function
code
code
code
code
Name
Name
Name
Name Setting
Setting
Setting
Setting range
range
range
range
F5.0 9
ON-OFF filter
times
0~10 5
This parameter is used to set filter strength of
terminals (S1~S 7 , HDI). When interference is
heavy, user should increase this value to prevent
malfunction.
Function
Function
Function
Function
code
code
code
code
Name
Name
Name
Name Setting
Setting
Setting
Setting range
range
range
range
F5. 10
Terminal
control mode
0~3 0
This parameter defines four different control
modes that control the inverter operation through
external terminals.
0: 2-wire control mode 1: Integrate REV / FWD
command with run direction.
K1 K2 Run command
OFF OFF Stop