Specifications
JiaXing Jarol Scientific Instrument Co.,Ltd - JR 6 000 series product s
58
Deceleration
mode
T he frequency changing method during the
running and starting of the inverter.
0: Linear
O utput frequency will increase or decrease with
fixed acceleration or deceleration time.
1: Reserved
Function
Function
Function
Function
code
code
code
code
Name
Name
Name
Name Setting
Setting
Setting
Setting range
range
range
range
F1.06 Stop mode
0~1 【 0 】
0: Deceleration to stop
When the stop command takes effect, the inverter
decreases the output frequency and the defined
deceleration time till stop.
1: Coast to stop
When the stop command takes effect, the inverter
blocks the output immediately. The motor coasts
to stop by its mechanical inertia.
Function
Function
Function
Function
code
code
code
code
Name
Name
Name
Name Setting
Setting
Setting
Setting range
range
range
range
F1.07 Starting 0.00~F0.03
frequency of
DC braking
【 0.00Hz 】
F1.08
Waiting time
before DC
braking
0.0~50.0s
【 0.0s 】
F1.09
DC braking
current
0.0~150.0%
【 0.0% 】
F1.10
DC braking
time
0.0~50.0s
【 0.0s 】
Starting frequency of DC braking: Start the DC
braking when running frequency reaches starting
frequency determined. Starting frequency of DC
braking is 0 and the DC braking is invalid . T he
inverter will stop in the defined DEC time.
Waiting time before DC braking: Inverter blocks
the output before starting the DC braking. After
this waiting time, the DC braking will be started so
as to prevent over-current fault caused by DC
braking at high speed.
DC braking current: The value is the percentage of
rated current of inverter. The bigger the DC
braking current is , the greater the braking torque