control system should use common pole grounding, and different devices connected by same power
cable should use series-wound grounding.
4.4.3.4
4.4.3.4
4.4.3.4
4.4.3.4 Leakage
Leakage
Leakage
Leakage Current
Current
Current
Current
Leakage current includes line-to-line leakage current and over-ground leakage current. Its value
depends on distributed capacitances and carrier frequency of inverter. The over-ground leakage current,
which is the current passing through the common ground wire, can not only flow into inverter system but
also other devices. It also can make leakage current circuit breaker, relay or other devices malfunction.
The value of line-to-line leakage current, which means the leakage current passing through distributed
capacitors of input output wire, depends on the carrier frequency of inverter, the length and section areas
of motor cables. The higher carrier frequency of inverter, the longer of the motor cable and/or the bigger
cable section area, the larger leakage current will occur.
Countermeasure
Countermeasure
Countermeasure
Countermeasure
Decreasing the carrier frequency can effectively decrease the leakage current. In the case of motor
cable is relatively long (longer than 50m), it is necessary to install AC reactor or sinusoidal wave filter at
the output side, and when it is even longer, it is necessary to install one reactor at every certain distance.
4.4.3.5
4.4.3.5
4.4.3.5
4.4.3.5 EMC
EMC
EMC
EMC Filter
Filter
Filter
Filter
EMC filter has a great effect of electromagnetic decoupling, so it is preferred for customer to install it.
For inverter, noise filter has following categories:
Noise filter installed at the input side of inverter;
Install noise isolation for other equipment by means of isolation transformer or power filter.
4.4.4 The installation complies with following standards: