Specifications

JiaXing Jarol Scientific Instrument Co.,Ltd JR 6 000 series product s
30
GND
Common ground terminal of analog signal and +10V.
GND must be isolated from COM.
HDO
High speed pulse or open collector output terminal. The corresponding
common terminal is COM.
Output frequency range: 0~50 kHz
AO1 AO2
analog output terminals, of which AO1 can be selected to voltage output or
current output by J3; AO2 can be selected to voltage output or current
output by J4.
Output range voltage(0~10V) /current (0~20mA)
RA RB RC
R relay output RA common RB NC RC NO.
Contact capacity AC250V/3A DC30V/1A
TA
RB TC
T relay output
TA
common TB NC TC NO
Contact capacity AC250V/3A DC30V/1A
+ RS485 -
485 communication port. 485 differenticial signal, +,-. Please use twisted
pairs and shiled cables on the standard communication port.