Specifications
JAROL Assumes the promotion of energy-saving technology as its own task!
29
4.
4.
4.
4. 3
3
3
3 .
.
.
. 2
2
2
2 Control circuit terminals
Figure 4 - 10 Control circuit terminals
4.
4.
4.
4. 3
3
3
3 .
.
.
. 3
3
3
3 Control circuit terminals explain
Terminal
Terminal
Terminal
Terminal Description
Description
Description
Description
S1 ~ S7
ON-OFF signal input, optical coupling with PW and COM.
Input voltage range: 9~30V
Input impedance: 3.3k Ω
HDI
High speed pulse or ON-OFF signal input, optical coupling with PW and
COM.
Pulse input frequency range: 0~50kHz
Input voltage range: 9~30V
Input impedance: 1.1k Ω
PLC
External power supply. +24V terminal is connected to PW terminal as
default setting. If the external power supply is needed, disconnect +24V
terminal with PLC terminal and connect PLC terminal with external power
supply.
P24
Local power supply of +24V( current: 150mA)
COM The common terminal of +24V
AI1
Analog input; -10V~10V
Input impedance: 20k Ω
AI2
Analog input, 0~10V/ 0~20mA , switched by J16.
Input impedance: 10k Ω (voltage input) / 250 Ω (current input)
+10V +10V for the inverter.