grounding wire should be short with a thick
diameter, and it is better to use multi-wires which
have copper core (>3.5mm2). When multiple
inverters need to be grounded, it is
recommended to use command grounding wire
for the avoidance of loop the ground wire.
4.3WiringControlCircuit
4.3WiringControlCircuit
4.3WiringControlCircuit
4.3WiringControlCircuit terminal
terminal
terminal
terminal
connect
connect
connect
connect
4. 3 .1 Precautions
The cable connected to the control terminal
should be left away from the main circuit and
strong current circuits (including power supply
cable, motor cable, relay and contactor
connecting cable) at least 20cm and parallel
wiring should be avoided. It is suggested to
apply perpendicular wiring to prevent inverter
malfunction caused by external interference.