Specifications

JiaXing Jarol Scientific Instrument Co.,Ltd JR 6 000 series product s
14
Product functions
Important function
RPM track Torque limitation Multi-step speed automatic
self-adjustment Slip compensate PID adjust Sagged control
Current control Torque boost Multifunctions input /output
terminal
Frequency given
way
Keyboard upper computer Analog AI1/AI2 Terminal pulse HDI
Multi-step speed and PLC PID , The combination of multi-modes
and the switch between different modes can be realized .
Frequency Range 0.00-400.00Hz
Acc and Dec time 0.1-3600.0s
Dynamic braking
DC braking start frequency 0.00-400.00Hz DC braking current
0.0-150% DC braking time 0.0-50.0s Noneed for DC braking
start waitting time,realize quickly braking
Special function
Multifunctions
shortcut key
Multifunctions shortcutkey can be seted for these operation JOG
inching REV and FWD Clear UP/DOWN set left shift key
display the status Quickly debug mode
Multi menu mode Basic menu mode Fast menu mode
Common D C bus
Many frequency inverters Common DC bus Energy automatic
equilibrium
Swing frequency
control
Multi pyramidal wave frequency control
Counting control Counting function
Protection
function
Overcurrent Overvoltage Undervolage Over temp Phase lack Overload
Environment
Operation Place
Indoor hide sunshine No dust Corrosive gas combustible gas
Oil mist Water vapor salinity
Altitude <1000m
Temperature
10 ~ 40 temperature at 40 ~50 Drop the forehead
use
Humidity <95%RH No droplet
Vibration <5.9m/s2 0.6g
Stock 20 ~ 60