Fault
Fault
Fault
Fault
Code
Code
Code
Code
Fault
Fault
Fault
Fault Type
Type
Type
Type Reason
Reason
Reason
Reason Solution
Solution
Solution
Solution
and the standard parameter is
huge
4. A utotune overtime
the parameters
EEP EEPROM fault
1. E rror of controlling the write
and read of the parameters
2. D amage to EEPROM
1. Press STOP/RST to reset
2. Ask for service
PIDE PID feedback fault
1. PID feedback offline
2. PID feedback source
disappear
1. Check the PID feedback signal
wires
2. Check PID feedback source
bE Braking unit fault
1. B raking circuit fault or
damage to the braking pipes
2. The external braking
resisitor is a little low
1. Check the braking unit and
change new braking pipes
2. Increase the braking resistor
END
Time reach of
factory setting
1. Trial time arrival 1. Ask for service
OL3 Overtorque
1. The acceleration is too fast
2. Reset the rotating motor
3. The voltage of the power
supply is too low.
4. The load is too heavy.
1. Increase the ACC time
2. Avoid the restarting after
stopping.
3. Check the power of the supply
line