Installation manual
84
Operating the PV inverter
Figure 7.25.: Q(V) settings page
Adjustable parameters
Parameter Menu Name Adjustable values Description
Lower Q/Sn Qi Limit 0 ... 60% Must be within the range Ind 60%
... Cap 60%
inductive | capacitive
Upper Q/Sn Qs Limit 0 ... 60% Must be within the range Ind 60%
... Cap 60%
inductive | capacitive
Lower capaci-
tive point
V2i 184 ... 264 V
Upper capaci-
tive point
V1i 184 ... 264 V For DE MVD the default V1i =
V1s = 230 V
Lower inductive
point
V1s 184 ... 264 V
Upper inductive
point
V2s 184 ... 264 V
Delay time 0 ... 10 s
Lock-in Power not applicable Not used for DE MVD
Lock-out Power not applicable Not used for DE MVD
Mode ON I OFF This switches the feature on and
off
7.3.6.3.7 Fault Ride Through (FRT)
This feature is available for MVD grids only.
This feature allows the Fault Ride Through features to be set.