Decommissioning
11. Decommissioning
Decommissioning Procedure
If it is necessary to put the SOLIVIA TL out of operation for return or maintenance, please follow
the instructions below:
WARNING
Death and serious injury may occur.
To avoid injuries, please follow the below procedures:
1. Switch off AC circuit breaker to disconnect with electrical grid.
2. Switch off the DC Disconnect switch to disconnect with DC power
input.
3. Use the proper voltage meter to conrm that the AC and DC power
connections are void of any current.
4. Remove the AC wiring immediately to completely disconnect with
electrical grid.
5. Remove the DC wiring to disconnect with PV array.
6. Remove the Communication module RS485 with the computer con-
nection.
7. After nishing all the procedures, you can remove the SOLIVIA TL
inverter from the mounting bracket.