Service manual

Printed in U.S.A.
Page 9
ProFloSE Downflow
Master Programming Mode
Entering Master Programming Mode
With the Time of Day Display set to 12:01 P.M., push and hold for 5 seconds both the Set Up and Set Down Buttons. The Program
Indicator will turn on to signal that this mode is entered. In this mode all possible option settings may be viewed.
1. US/Metric Display Format (U)
This display is used to set the desired display format. This option setting is identified by the letter (U) in the first digit. There
are three possible settings:
Example:
[ U - - 1 ] for US gallons
Metric format uses liters or cubic meters with a 24-hour timekeeping format. Regeneration timing in tenths of minutes.
Example:
[ U - - 2 ] for liters
[ U - - 4 ] for cubic meters
The SET UP or DOWN buttons will adjust this value.
Depress the Extra Cycle Button to proceed to the next step.
2. Regeneration Type (7)
Depress the Extra Cycle Button. This display is used to set the Regeneration Type. This option setting is identified by the
number 7 in the first digit. There are 3 possible settings:
Timeclock Delayed. The control will determine that regeneration is required when the set Regeneration Time has been
reached. The Regeneration Day Override setting will determine which days a regeneration cycle will be initiated.
Example:
[ 7 - - 1 ]
Meter Immediate. The control will determine that regeneration is required when the available volume of softened water drops
to or below zero. Regeneration to begin immediately.
Example:
[ 7 - - 2 ]
Meter Delayed. The control will determine that a regeneration is required when the available volume of softened water drops
to or below zero. Regeneration is to begin immediately at the set Regeneration Time.
Example:
[ 7 - - 3 ]
The Set UP and DOWN Buttons will adjust this value.