User Manual

27
Wiring
English
2. Connecting the DC Power Cord
Field wiring terminal marking for wire type (75°C (167 °F) Copper conductors
only)
*1 If the conductor’s end (individual) wires are not twisted correctly, the end
wires may either short against each other or against an electrode.
3 Remove screws from the L, N, and FG (functional ground)
terminals. Attach the ring terminals and reinsert the screws.
Check each wire to make sure the connections are correct.
Note :
Terminal Block: 1.4 N•m (12.4 lb•in.)
FG (functional ground) Terminal: 1.4 N•m (12.4 lb•in.)
4 Close the terminal strip’s clear plastic cover.
Power Cord Diameter
0.75 to 2.5 mm
2
(18-13 AWG)
Conductor type
Simple or Stranded Wire
*1
Conductor length
)*
mm
in.
10
0.39