User guide

3
Environmental Specifications
External Specifications
Serial Interface Specifications
RS-232C Isolation Unit
The RS-232C/RS-422 type.
D-Sub 9-pin plug connector's pin assignments are as follows.
Use the DIP switch on the unit to change communication methods.
For Display side settings please refer to “Display side settings”.
Physical Environment
Ambient Operating
Temperature
0...50 °C (32...122 °F)
Storage Temperature -20...60 °C (-4...140 °F)
Ambient and Storage
Humidity
10...90 % RH (Non condensing, wet bulb
temperature 39 °C [102.2 °F] or less)
Dust 0.1 mg/m
3
(10
-7
oz/ft
3
) or less (non-conductive levels)
Pollution Degree For use in Pollution Degree 2 environment
Atmosphere Free of corrosive gases
Atmospheric Pressure
(Operating Altitude)
800...1114 hPa (2000 m [6561 ft] or lower)
Mechanical
Environment
Vibration Resistance
IEC/EN 61131-2 compliant
5...9 Hz Single amplitude 3.5 mm (0.14 in.)
9...150 Hz Fixed acceleration: 9.8 m/s
2
X, Y, Z directions for 10 cycles (100 min.)
Concussion Resistance
IEC/EN 61131-2 compliant
(147 m/s
2
, X, Y, Z directions for 3 times)
Electrical
Environment
Noise immunity
Noise Voltage: 1000 Vp-p
Pulse Width: 1 µs
Rise Time: 1 ns
(via noise simulator)
Electrostatic Discharge
Immunity
Contact Discharge Method: 6 kV (IEC/EN61000-4-2
Level 3)
Cooling Method Natural air circulation
Weight 170 g (0.37 lb) or less
External
Dimensions
W110 x H40 X D27 mm (W4.33 x H1.57 x D1.06 in.)
RS232C
RS422