Owner manual
4/7
Installation, Operation and Maintenance
Make sure you follow all the recommendations in the GP4000 Series
Installation Guide and additionally those listed below.
DANGER
POTENTIAL FOR EXPLOSION
• Confirm that the location is free from explosively hazardous gases or
dust before connecting or disconnecting equipment, replacing or
wiring modules.
• The ambient temperature in protective enclosure must not exceed
50°C or 55°C (refer to marking).
• Confirm each interface (COM1, COM2, LAN), field wiring terminal
blocks and the SD Card / Battery Cover have been securely locked.
• Confirm USB cables are attached with its appropriate clamp.
• Modules must be installed in a protective enclosure that provides at
least the following degree of protection:
- IP54 for atmosphere with gas
- IP6x for atmosphere with dust
• Do not open the protective enclosure while the system is powered up.
• Confirm that the power supply has been turned OFF before
disconnecting, replacing or wiring modules.
• Ensure that the FG (Functional Ground) on the power supply is
properly connected to ground.
• Use only screw fasteners suitable for installations in explosive
atmospheres.
• Do not use damaged equipment.
• Use Touch Pen CA7-TPPEN/ALL-01 on all GP4000 Series used in
zone 2 and zone 22 areas.
Failure to follow these instructions will result in death or serious injury.