Instruction Manual

13
To avoid an electric shock, when connecting the FP’s power cord terminals to
the power terminal block, confirm that the FP’s power supply is completely
turned OFF, via a breaker, or similar unit.
To avoid the dangers of fire, electric hazards and equipment damage, be sure
to use only the specified voltage when operating the FP.
Since there is no power switch on the FP unit, be sure to attach a breaker-type
switch to its power cord.
Electrical Specification
Environmental Specification
6 Wiring
Item Specification
Power Supply
Type DC Type AC
Rated Voltage DC24V AC100 ~ 240V
Allowable Voltage DC19.2 ~ 28.8V AC85 ~ 265V
Rated Frequency - 50 / 60HZ
Allowable Frequency
Range
- 40 ~ 72Hz
Allowable Voltage Drop 10 ms (Max.)
1 cycle or less
(Voltage Drop Interval is
1s or more)
Power
Consumption
FP-3500T
Series
DC 24V 2.08A (or less)
(TYP 1.08A)
AC100V 0.90A or less
(TYP 0.55A)
AC240V 0.45A or less
(TYP 0.30A)
FP-3600T
Series
DC 24V 2.08A (or less)
(TYP 1.30A)
FP3650-
T41
-
In-Rush Current 30A (Max.) 60A (Max.)
Voltage Endurance
AC1000V 20mA
1 for minute
(between charging and
FG terminals)
AC1500V 20mA
for 1 minute
(between charging and
FG terminals)
Insulation Resistance
DC500V 10M (Min.)
(between charging and
FG terminals)
DC500V 10M (Min.)
(between charging and
FG terminals)
Item Specification
Surrounding Air
Temperature
0 ~ 50ºC (The panel should not incline more than 30º)
Storage Temperature -20 ~ +60ºC
Ambient Humidity
10 ~ 90%RH
(No condensation, Wet bulb temperature: 39ºC max.)
Storage Humidity
Air Purity (Dust) 0.1mg/m
3
(Max.) (No electrically conductive dust is allowed)
Pollution Degree For use in Pollution Degree 2 environment