Instruction Manual
13
• To avoid an electric shock, when connecting the FP’s power cord terminals to
the power terminal block, confirm that the FP’s power supply is completely
turned OFF, via a breaker, or similar unit.
• To avoid the dangers of fire, electric hazards and equipment damage, be sure
to use only the specified voltage when operating the FP.
• Since there is no power switch on the FP unit, be sure to attach a breaker-type
switch to its power cord.
Electrical Specification
Environmental Specification
6 Wiring
Item Specification
Power Supply
Type DC Type AC
Rated Voltage DC24V AC100 ~ 240V
Allowable Voltage DC19.2 ~ 28.8V AC85 ~ 265V
Rated Frequency - 50 / 60HZ
Allowable Frequency
Range
- 40 ~ 72Hz
Allowable Voltage Drop 10 ms (Max.)
1 cycle or less
(Voltage Drop Interval is
1s or more)
Power
Consumption
FP-3500T
Series
DC 24V 2.08A (or less)
(TYP 1.08A)
AC100V 0.90A or less
(TYP 0.55A)
AC240V 0.45A or less
(TYP 0.30A)
FP-3600T
Series
DC 24V 2.08A (or less)
(TYP 1.30A)
FP3650-
T41
-
In-Rush Current 30A (Max.) 60A (Max.)
Voltage Endurance
AC1000V 20mA
1 for minute
(between charging and
FG terminals)
AC1500V 20mA
for 1 minute
(between charging and
FG terminals)
Insulation Resistance
DC500V 10MΩ (Min.)
(between charging and
FG terminals)
DC500V 10MΩ (Min.)
(between charging and
FG terminals)
Item Specification
Surrounding Air
Temperature
0 ~ 50ºC (The panel should not incline more than 30º)
Storage Temperature -20 ~ +60ºC
Ambient Humidity
10 ~ 90%RH
(No condensation, Wet bulb temperature: 39ºC max.)
Storage Humidity
Air Purity (Dust) 0.1mg/m
3
(Max.) (No electrically conductive dust is allowed)
Pollution Degree For use in Pollution Degree 2 environment