Instruction Manual

10
Wiring
To avoid an electric shock, when connecting the FP’s power cord terminals to the power ter-
minal block, confirm that the FP’s power supply is completely turned OFF, via a breaker, or
similar unit.
To avoid the dangers of fire, electric hazards and equipment damage, be sure to use only the
specified voltage when operating the FP.
Since there is no power switch on the FP unit, be sure to attach a breaker-type switch to its
power cord.
Electrical Specification
Environmental Specification
Power Cord Specifications
Use copper conductors only.
Item Specification
Power Supply
Rated Voltage AC100V ~ AC240V
Allowable Voltage AC85V ~ AC264V
Rated Frequency 50 / 60HZ
Allowable Frequency
Range
40Hz - 72Hz
Allowable Voltage Drop 1 cycle (Max.)
(Voltage drop interval must be 1s or more.)
Current Consumption
AC100V 1.1A or less (TYP 0.75A)
AC240V 0.7A or less (TYP 0.44A)
In-Rush Current 60A (Max.)
Voltage Endurance
AC1500V 20mA for 1 minute
(between charging and FG terminals)
Insulation Resistance
DC500V 10M (Min.)
(between charging and FG terminals)
Item Specification
Surrounding Air Temperature 0 ~ 50ºC (The panel should not incline more than 30º)
Storage Temperature -20 ~ +60ºC
Ambient Humidity
10 ~ 90%RH
(No condensation, Wet bulb temperature: 39ºC max.)
Storage Humidity
Air Purity (Dust)
0.1mg/m
3
(Max.) (No electrically conductive dust is
allowed)
Pollution Degree For use in Pollution Degree 2 environment
Power Cord Diameter 0.75mm
2
to 2.5mm
2
(18AWG to 12 AWG)
Conductor Type Simple or Twisted Wire
*1
Conductor Length
10mm [0.39 in.]