User Manual

Chapter 2 Specifications
2-35
General-Purpose Input (DIN 0 to 3, RST)
Input Voltage DC12V to 24V
Input Method Sink / Source Input
Input Current 10mA ( DC24V )
Input Resistance 3.6k
Input Points
5 points ( common with external
reset input )
Operation
Range
ON voltage DC10V or more
OFF voltage DC3V or less
Isolation Method Photocoupler Isolation
Dielectric Strength Voltage 500V or more
General-Purpose Input (DIN) level must be 1.5 seconds or longer to be
detected.It may detect under 1.5 seconds.
Be sure the voltage value between terminals is controlled via the input voltage, so
that the PS-A is operated within its recommended range. If the input voltage
exceeds this range, a malfunction or PS-A damage may occur.
With Sink/Source input, even if the DIN(-), and RST(-) are positive, and DIN(+),
RST(+) are negative, no problems are created. Be sure to operate the unit within
the recommended voltage range.
(Interface Circuit)
+5V
1.8k
1/10W
1.8k
1/10W
R
R
PC357
No polarity - for Sink /
Source input
switch or other
switching device
Cable
DC12V
to 24V
RST(+) pin # 5
DIN0(+) pin # 6
DIN1(+) pin # 13
DIN2(+) pin # 16
DIN3(+) pin # 18
RST(-) pin # 11
DIN0(-) pin # 12
DIN1(-) pin # 17
DIN2(-) pin # 23
DIN3(-) pin # 24