User Manual
PL3000 Series Hardware Manual
3-14
General Purpose Signal Input (DIN 0, 1)
Input Voltage DC12V to 24V
Input Method Sink / Source Input
Input Current 10mA ( DC24V )
Input Resistance 3.6kΩ
Input Points
2 points ( common with external
reset input )
Operation
Range
ON voltage DC10V or more
OFF voltage DC3V or less
Isolation Method Photocoupler Isolation
Dielectric Strength Voltage 500V or more
• General-Purpose Input (DIN) level must be 1.5 seconds or longer to be detected.
It may not detect under 1.5 seconds.
• Be sure the voltage value between terminals is controlled via the input voltage, so
that the PL is operated within its recommended range. If the input voltage
exceeds this range, a malfunction or PL damage may occur.
• With Sink/Source input, even if the DIN(-), and RESET(-) are positive, and
DIN(+), RESET(+) are negative, no problems are created. Be sure to operate the
unit within the recommended voltage range.
+5V
1.8k
Ω
1/10W
1.8k
Ω
1/10W
R
PC357
No polarity - for Sink /
Source input
switch or other
switching device
Cable
DC12V
to 24V
DINCOM pin # 9
DIN0(+) pin # 4
DIN1(+) pin # 5
(Interface Circuit)
R