User Manual
16
• T ightening the screws with too much
force can damage the PL unit.
• Be sure to insert installation fasteners
in the recessed portion of an installa-
tion fasteners hole. If the fastene rs are
not correctly attache d, th e PL unit may
shift or fal l out of the panel.
2. PL-3600*/3700*/3900T Series
Installation
• Before installing the PL unit on the
panel, detach the control box from the
front module to configure the settings
of the internal switches.
Installation Requirements
• For easier maintenance, operation, and
improved ventilation, be sure to install the
PL at least 50mm [1.97 in.] away from
adjacent structures and other equipment.
For the face to which the cable is con-
nected, however, a space of 120 mm [4.72
in.] or more is necessary for cable curve.
• Be sure that the surrounding air tempera-
ture and the ambient humidity are within
their specified ranges.
When installing the PL on the panel of a
cabinet or enclosure, “Surrounding air
temperature” indicates both the panel face
and cabinet or enclosure’s internal temper-
ature.
• Be sure that heat from surrounding equip-
ment does not cause the PL to exceed its
standard operating temperature.
Installation
(1) Create a Panel Cut using the dimensions
in the following table. Also, determine
the panel thickness according to the panel
thickness range with due consideration of
panel strength.
• When using the PL-3600K series to
replace the 3612KPM/4612KPM from
Xycom Automation, you can install the
SEE
Installation/uninstallation of the
front module and the contr ol
box, Internal Switches
Unit:mm[in.]
120
[4.72]
50
[1.97]
50
[1.97]
50
[1.97]
50
[1.97]
50
[1.97]
50
[1.97]
PL X Y
Panel
thickness
PL-3600T
Series
295.5
[11.61 ]
243.5
[9.59 ]
1.6[0.06] to
10.0[0.39]
PL-3600K
/3700T
Series
383.5
[15.1 ]
282.5
[11.12 ]
1.6[0.06] to
10.0[0.39]
PL-3700K
Series
441.5
[17.38 ]
313.5
[12.34 ]
1.6[0.06] to
10.0[0.39]
PL-3900T
Series
419.5
[16.52 ]
352.5
[13.88 ]
1.6[0.06] to
10.0[0.39]
Panel face
Cabinet
interior
30
[1.18]
30
[1.18]
unit:mm[in.]
50
[1.97]
PL
X
Unit:mm[in.]
Y
Under
4-R3[0.12]
Panel
thickness
+1
-
0
+
0.04
-
0
+1
-
0
+
0.04
-
0
+1
-
0
+
0.04
-
0
+1
-
0
+
0.04
-
0
+1
-
0
+
0.04
-
0
+1
-
0
+
0.04
-
0
+1
-
0
+
0.04
-
0
+1
-
0
+
0.04
-
0