User Manual
14
Installations
1. PL-3000B Series Installation
Installation Requirements
• For easier maintenance, operation, and improved ventilation, be sure to install the PL at least
50mm [1.97 in.] away from adjacent structures and other equipment. 120 mm [4.72 in.] space
(minimum) is necessary at the front for cable curve.
• Be sure that the surrounding air temperature and the ambient humidity are within their specified
ranges.
Check the surrounding air temperature 30 mm [1.18 in.] away from the main unit.
• Be sure that heat from surrounding equipment does not cause the PL to exceed its standard
operating temperature.
Horizontal mounting
(Front)
50
[1.97]
50 [1.97]
50 [1.97]
Unit:mm[in.]
50 [1.97]
50
[1.97]
50
[1.97]
Horizontal mounting
(Right side)
50
[1.97]
50 [1.97]
120
[4.72]
Vertical mounting
(Front)
Vertical mounting
(Right side)
50
[1.97]
50
[1.97]
120
[4.72]
120
[4.72]
50 [1.97]
50 [1.97]
50
[1.97]
50[1.97]
50[1.97]
50
[1.97]
Wall mounting
(Front)
Wall mounting
(Left side)
Ex.: Horizontal mounting
30
[1.18]
30 [1.18]
30
[1.18]
U
n
i
t:mm
[i
n.
]
30
[1.18]
30 [1.18]
30
[1.18]