User Manual

14
Installations
1. PL-3000B Series Installation
Installation Requirements
For easier maintenance, operation, and improved ventilation, be sure to install the PL at least
50mm [1.97 in.] away from adjacent structures and other equipment. 120 mm [4.72 in.] space
(minimum) is necessary at the front for cable curve.
Be sure that the surrounding air temperature and the ambient humidity are within their specified
ranges.
Check the surrounding air temperature 30 mm [1.18 in.] away from the main unit.
Be sure that heat from surrounding equipment does not cause the PL to exceed its standard
operating temperature.
Horizontal mounting
(Front)
50
[1.97]
50 [1.97]
50 [1.97]
Unit:mm[in.]
50 [1.97]
50
[1.97]
50
[1.97]
Horizontal mounting
(Right side)
50
[1.97]
50 [1.97]
120
[4.72]
Vertical mounting
(Front)
Vertical mounting
(Right side)
50
[1.97]
50
[1.97]
120
[4.72]
120
[4.72]
50 [1.97]
50 [1.97]
50
[1.97]
50[1.97]
50[1.97]
50
[1.97]
Wall mounting
(Front)
Wall mounting
(Left side)
Ex.: Horizontal mounting
30
[1.18]
30 [1.18]
30
[1.18]
U
n
i
t:mm
[i
n.
]
30
[1.18]
30 [1.18]
30
[1.18]