Instruction Manual
7
These products conform to the following
standards:
UL60950-1
Information Technology Equipment
- Safety - Part 1
UL1604
Electrical Equipment for use in Class I and II,
Division 2, and Class III Hazardous
(classified) locations.
CAN/CSA-C22.2 No.60950-1-03
(c-UL approval)
Information Technology Equipment
- Safety - Part 1
CSA-C22.2 No.213-M1987
(c-UL approval)
Non-incendive Electrical Equipment for Use
in Class I, Division 2 Hazardous Locations.
The following units are UL/c-UL/CSA listed
products.
(UL File No.E220851, UL File No.E210412,
CSA File No.219866)
These products conform to the following
standards:
UL508
Industrial Control Equipment
UL1604
Electrical Equipment for use in Class I and II,
Division 2, and Class III Hazardous
(classified) locations.
CSA-C22.2 No.14-M95
Industrial Control Equipment
CSA-C22.2 No.213-M1987
Non-Incendive Electrical Equipment for Use
in Class I, Division 2 Hazardous Locations
<Cautions>
Be aware of the following items when
building the GP into an end-use product:
• The GP unit's rear face is not approved as
an enclosure. When building the GP unit
into an end-use product, be sure to use an
enclosure that satisfies standards as the
end-use product's overall enclosure.
• The GP unit must be used indoors only.
• Install and operate the GP with its front
panel facing outwards.
• If the GP is mounted so as to cool itself
naturally, be sure to install it in a vertical
panel. Also, it's recommended that the GP
should be mounted at least 100mm away
from any other adjacent structures or
machine parts. The temperature must be
checked on the final product in which the
GP is installed.
• Serial Interface (COM2) is not Limited
Power Source.
UL1604/CSA-C22.2, No.213 -
Compliance and Handling Cautions
(1) Power and input/output wiring must be in
accordance with Class I, Division 2 wiring
methods - Article 501-4(b) of the National
Electrical Code, NFPA 70 within the
United States, and in accordance with
Section 18-152 of the Canadian Electrical
Code for units installed within Canada.
(2) Suitable for use in Class I, Division 2,
Groups A, B, C, and D Hazardous
Locations, or Non-Hazardous Locations.
(3) WARNING: Explosion hazard-
substitution of components may impair
compliance to Class I, Division 2.
(4) WARNING: Explosion hazard-when in
hazardous locations, turn the power OFF
before replacing or wiring modules.
Product Model No.
UL/c-UL/CSA
Registration
Model No.
AGP3500-S1-D24-CA1M
*1
*1 The sales area is limited.
3280024-22
AGP3500-T1-D24-CA1M 3280035-41
AGP3600-T1-D24-CA1M 3280024-14