Manual

9
Installations
1. Installation Requirements
For easier maintenance, operation, and
improved ventilation, be sure to install the
GP at least 100 mm [3.94 in.] away from
adjacent structures and other equipment.
Be sure that the surrounding air tem-
perature and the ambient humidity are
within their designated ranges. (Sur-
rounding air temperature: 0 to 50 °C,
Ambient humidity: 10 to 90 %RH, Wet
bulb temperature: 39 °C max.)
When installing the GP on the panel of
a cabinet or enclosure, “Surrounding
air temperature” indicates both the
panel face and cabinet or enclosure’s
internal temperature.
Be sure that heat from surrounding equip-
ment does not cause the GP to exceed its
standard operating temperature.
2. GP Installation
(1) Create a Panel Cut and insert the GP
into the panel from the front.
(2) Confirm that the installation gasket is
attached to the GP unit and then place
the GP unit into the Panel from the front.
It is strongly recommended that you use
the installation gasket, since it absorbs
vibration in addition to repelling water.
For the procedure for replacing the installa-
tion gasket, refer to “GP3000 Series Hard-
ware Manual”.
(3) The following figures show the four (4)
fastener insertion slot locations. (Only the
AGP-3750T has eight (8) slot locations.)
Insert each fastener’s hook into the slot
and tighten it with a screwdriver. Insert the
installation fasteners securely into the
insertion slot recess.
100
[3.94]
100
[3.94]
100
[3.94]
100
[3.94]
Unit:mm[in.]
100
[3.94]
100
[3.94]
100
[3.94]
Panel Face
Inside Cabinet
GP X Y
Panel
thickness
AGP-3500T
AGP-3510T
AGP-3550T
AGP-3560T
259.0
[
10.20
]
201.0
[
7.91
]
1.6 [0.06]
to
10.0 [0.39]
AGP-3500L
AGP-3500S
AGP-3600T/U
AGP-3650T/U
301.5
[
11.87
]
227.5
[
8.96
]
AGP-3750T
383.5
[
15.10
]
282.5
[
11.12
]
Unit: mm [in.]
X
r
3 [0.12]
Panel
thickness
GP
Y
+1
-0
+0.04
-0
+1
-0
+0.04
-0
+1
-0
+0.04
-0
+1
-0
+0.04
-0
+1
-0
+0.04
-0
+1
-0
+0.04
-0