Wiring
indicates a fuse.
The power for the analog module should be supplied separately from the LT. Turn
the analog module on before turning the LT on. Wait at least 30 seconds after
power-off to restart the external power-supply or it may not operate properly.
Use the braid supplied with the module to connect the functional ground.
Connect an appropriate fuse for the applied voltage and current draw, at the position
shown in the diagram.
To avoid disturbances on the analog outputs, the power supply of the EXM-AVO2HT
module must be turned on or off at the same time than the base controller power supply.
15.11 2-ch analog-input/1-ch analog-output module
The detail of the external power supply is: the rated supply voltage is 24 VDC, the rated
input voltage ranges from DC20.4 to 28.8 V The consumption current is 45 mA
*1
or
50 mA
*2
(24VDC) when the input is not-open, output 100%. You can select either voltage or
current for each inpu or output channel.
EXM-AMM3HT
Characteristics of Analog Voltage Inputs Voltage Input Current Input
Input Range From DC0 to 10V From DC4 to 20 mA
Input Impedance 1 M min. 10
Input Points 2 points
A-D
Conversion
Sample Repetition Time 20 ms max.
Total Input System Transfer
Time
*
3
105 ms + 1 scan time*
1
60 ms + 1 scan time*
2
Input Type Single-ended input Differential input
Operating Mode Self-scan
Conversion Mode  type ADC
(1)
(1)
+
-
0 V
+
0 V
0 V
0 V
0 V
+
0 V
0 V
(1) Voltage/current preactuator
OUT1
OUT 2
<EXM-AVO2HT>