Specifications

Installation
UMMBRG300-1101 7
Avoid dusty environments.
Avoid shock or vibration
Do not exceed the specified operational temperatures and humidity range.
Mount inside an electrical switchboard or control cabinet.
Make sure there is sufficient air ventilation and clearance to other devices mounted
next to the unit.
Observe applicable local regulations like EN60204 / VDE0113.
Powering the MBRG-300
Before connecting power please follow the rules in the section called “Safety Precau-
tions” and the section called “Before connecting anything”.
Power is supplied via a 3.81 mm 2-pin pluggable terminal block located at the top side
of the mounted unit (refer to Figure2.1, “Location of connectors”). The following table
and picture shows the power terminal socket pinout:
V+
V-
1
Pin Signal Function
1 V+ Positive voltage supply (10 - 30 V DC)
2 V- Negative voltage supply, DC power return
Table 3.1: Power supply connector pinout
Make sure that the polarity of the supply voltage is correct before connecting any
device to the serial ports! A wrong polarity can cause high currents on the ground
plane between the V- power supply pin and the serial port ground pins, which can
cause damage to the device.
Wiring the RS-485/422 interface
The RS-485/422 port is used for integrating the MBRG-300 into a two-wire or four-wire
Modbus over Serial Line network. The use of either the RS-485 or RS-422 interface must
be configured using the web interface (See the section called “Configuring serial line
Modbus”). The MBRG-300 is a Modbus Master device on this interface.
Wiring the RS-232 interface
The RS-232 port can alternativly be used for serial communication to a Modbus Slave
device instead of RS-485. The use of the RS-232 interface must be configured using the
web interface (See the section called “Configuring serial line Modbus”). The MBRG-300
is a Modbus Master device on this interface.