Specifications
Installation
UMMBRG300-1101 7
• Avoid dusty environments.
• Avoid shock or vibration
• Do not exceed the specified operational temperatures and humidity range.
• Mount inside an electrical switchboard or control cabinet.
• Make sure there is sufficient air ventilation and clearance to other devices mounted
next to the unit.
• Observe applicable local regulations like EN60204 / VDE0113.
Powering the MBRG-300
Before connecting power please follow the rules in the section called “Safety Precau-
tions” and the section called “Before connecting anything”.
Power is supplied via a 3.81 mm 2-pin pluggable terminal block located at the top side
of the mounted unit (refer to Figure2.1, “Location of connectors”). The following table
and picture shows the power terminal socket pinout:
V+
V-
1
Pin Signal Function
1 V+ Positive voltage supply (10 - 30 V DC)
2 V- Negative voltage supply, DC power return
Table 3.1: Power supply connector pinout
Make sure that the polarity of the supply voltage is correct before connecting any
device to the serial ports! A wrong polarity can cause high currents on the ground
plane between the V- power supply pin and the serial port ground pins, which can
cause damage to the device.
Wiring the RS-485/422 interface
The RS-485/422 port is used for integrating the MBRG-300 into a two-wire or four-wire
Modbus over Serial Line network. The use of either the RS-485 or RS-422 interface must
be configured using the web interface (See the section called “Configuring serial line
Modbus”). The MBRG-300 is a Modbus Master device on this interface.
Wiring the RS-232 interface
The RS-232 port can alternativly be used for serial communication to a Modbus Slave
device instead of RS-485. The use of the RS-232 interface must be configured using the
web interface (See the section called “Configuring serial line Modbus”). The MBRG-300
is a Modbus Master device on this interface.