© MHG Heating Ltd Installation and Operating Manual for the ProCon 16, 27, 47, 75 & 77 Wall Mounted Condensing Boiler Range. MHG Heating Ltd, Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey, KT20 5LR 0845 6448802 Telephone. 0845 6448803 Fax. Email info@mhgheating.co.uk Website www.mhgheating.co.uk 1 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd Section 1.0 1.1 1.2 1.3 1.4 1.5 2.0 2.1 3.0 3.1 3.2 3.3 3.4 3.5 3.6 4.0 4.1 5.0 6.0 7.0 8.0 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10 8.11 8.12 8.13 8.14 9.0 10.0 10.1 10.2 10.3 10.4 10.5 10.6 10.7 11.0 11.1 12.0 12.1 13.0 13.1 14.0 14.1 15.0 16.0 16.1 17.0 17.1 17.2 17.3 18.0 18.1 18.2 19.0 20.0 21.0 21.1 21.2 21.3 21.4 22.0 23.0 24.0 25.0 26.
© MHG Heating Ltd 1.0 Appliance Type There are four build types and four outputs within the ProCon range. Please ensure you have the correct unit for the application and where required located correctly within the cascade prior to beginning the installation. ProCon 16H & 16HS, ProCon 27H, 27S & 27HS, ProCon 47H & 47S, ProCon 75H & 75HM 1.
© MHG Heating Ltd 2.0 Installation Regulations and Requirements The installation of Procon HT boilers must be in accordance with the relevant requirements of Gas Safety (Installation & Use) Regulations 1994, Health & Safety at Work Act, Building Regulations, IEE Regulations, Construction (Design & Management) Regulations 1994, Local Authority Bye-Laws, National, Fire Regulations and Insurance Company requirements.
© MHG Heating Ltd 2.1 Appliance Warranties All MHG appliances enjoy a full 24 month warranty as detailed in our terms and conditions. The guarantee period shall begin on the day of commissioning, or at latest 3 months after delivery has been made.
© MHG Heating Ltd 3.0 Dimensions. 16 – 47 Boilers Legend 1 2 Cable Entry Grommets Heating Flow 22mm (All Models) 5 Hot Water Primary Return 22mm (HS Models) Cold Water Inlet 22mm (S Models) 6 Heating Return 22mm (All Models) 3 Hot Water Primary Flow 22mm (HS Models) Hot Water Outlet 22mm (S Models) 7 Condensate Outlet ¾” BSP Plastic 4 Gas Inlet 22mm 7.
© MHG Heating Ltd 3.1 Dimensions. 75 Boiler Legend A B C Condensate Cleanout Connection ¾” Cap Condensate Outlet ¾” BSP Plastic Heating Return 1 ¼” D E F Heating Flow 1 ¼” Gas Supply inlet ¾” Cable Entry Grommets 7 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 3.2 Dimensions. 77 Boiler Legend A B C D Heating Return Top Connection Option 1 ¼” Heating Return Bottom Connection Option 1 ¼” Heating Flow Top Connection Option 1 ¼” Heating Flow Bottom Connection Option 1 ¼” E F G H Condensate Outlet ¾” BSP Plastic Condensate Cleanout Connection ¾” Cap Cable Entry Grommets Gas Inlet ¾” 8 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.
© MHG Heating Ltd 3.3 Dimensions HS + Calorifier Below (Additional information available from the website www.mhgheating.co.uk) Legend VL WW Z KW Hot water Primary Flow 1” Hot Water Secondary Outlet ¾” Hot Water Secondary Return ½” Cold Water Secondary Inlet ¾” RL A B C Hot Water Primary Return 1” 120 Litre Calorifier Pipework Cover Calorifier Cover 3.3 Dimensions HS + Calorifier Adjacent (Additional information available from the website www.mhgheating.co.
© MHG Heating Ltd 3.4 Installation and Service Clearances 16-47 Boilers 10 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 3.4 Mounting Information 16 – 47 Boilers 11 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 3.5 Installation and Service Clearances 75 Boiler 12 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 3.5 Mounting Clearances 75 Boiler 13 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 3.6 Installation and Service Clearances 77 Boiler 14 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 3.6 Mounting Clearances 77 Boiler Please contact our Technical department for Guidance 15 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 4.0 Delivery and Mobility All ProCons are supplied fully tested and therefore may contain residual test water. The test water utilised contains additives that will help prevent the pump from sticking and other metals from oxidising. To maintain the structural integrity of the appliance the internal components should not be used during the lifting and positioning of the unit onto the wall bracket. All packaging materials should be disposed of in an environmentally way. 4.
© MHG Heating Ltd 5.0 Technical Data Technical Data Units 16 H & HS 27 H & HS & (S) 47 H & (S) 75 & 77 H & HM Nominal Heat Input Net Nominal Heat Input Gross Min/Max Min/Max kW kW 4.0/15.0 4.4/16.5 6.5/25.0 7.2/27.5 12.0/45.0 13.2/49.5 15.0/70.0 16.5/77.0 Carbon Emissions 100% Of max Output G20 G31 kgC/kWhr kgC/kWhr 0.061 0.078 0.061 0.078 0.061 0.078 0.060 0.077 Carbon Emissions 30% Of max Output SEDBUK Rating G20 G31 kgC/kWhr kgC/kWhr 0.055 0.070 B 0.055 0.070 B 0.055 0.070 B 0.
© MHG Heating Ltd 6.0 Pressure (Safety) Relief Valve In accordance with the prevailing British Standard 5440/6644, the installer shall install as suitably sized Pressure (Safety) Relief Valve.
© MHG Heating Ltd Enhanced electrical connection for ProCon HM (Units supplied with an integral Cascade manager) Legend High Voltage Output Terminals 230 Volts BW HK/ZB N E L N E L Neutral Terminal for Hot Water Charging Pump Earth Terminal for Hot Water Charging Pump 230 Volt Output For Hot Water Charging Pump (Max 1Amp) Neutral Terminal for Heating Circuit Pump Earth Terminal for heating Circuit Pump 230 Volt Output For Heating Circuit Pump (Max 1Amp) Low Voltage Control terminals < 25 Volts H1 RL
© MHG Heating Ltd 8.0 Hydraulic Design Single Unit (Option 1) Electrical Connections Single Unit (Option 1) Parameter # H554 b3 Parameters Description Weather Compensation (1) / Constant Flow Temperature Operation (0) Default Proposed Change 1 0 (E10 Error signal when outside air sensor is not installed.) 20 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 8.1 Hydraulic Design Single Unit (Option 2) Electrical Connections Single Unit (Option 2) Parameter # H554 b3 Parameters Description Weather Compensation (1) / Constant Flow Temperature Operation (0) Default Proposed Change 1 0 0 1 (E10 Error signal when outside air sensor is not installed.) H558 b2 Hot Water Storage Sensor (0) / Hot Water Thermostat (1) (E50 Error signal when sensor is not used.
© MHG Heating Ltd 8.2 Hydraulic Design Single Unit (Option 3), Electrical Connections Single Unit (Option 2) Parameter # H554 b3 Parameters Description Weather Compensation (1) / Constant Flow Temperature Operation (0) Default Proposed Change 1 0 0 1 (E10 Error signal when outside air sensor is not installed.) H558 b2 Hot Water Storage Sensor (0) / Hot Water Thermostat (1) (E50 Error signal when sensor is not used.
© MHG Heating Ltd 8.3 Hydraulic Design Single Unit (Option 4) Electrical Connections Single Unit (Option 4) Parameter # H554 b3 Parameters Description Weather Compensation (1) / Constant Flow Temperature Operation (0) Default Proposed Change 1 0 (E10 Error signal when outside air sensor is not installed.) 23 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 8.4 Hydraulic Design Single Unit (Option 5) Electrical Connections Single Unit (Option 5) Parameter # H554 b3 Parameters Description Weather Compensation (1) / Constant Flow Temperature Operation (0) Default Proposed Change 1 0 0 1 (E10 Error signal when outside air sensor is not installed.) H558 b2 Hot Water Storage Sensor (0) / Hot Water Thermostat (1) (E50 Error signal when sensor is not used.
© MHG Heating Ltd 8.5 Hydraulic Design Single Unit (Option 6) Electrical Connections Single Unit (Option 6) • Parameter # H554 b3 Parameters Description Weather Compensation (1) / Constant Flow Temperature Operation (0) H558 b2 Hot Water Storage Sensor (0) / Hot Water Thermostat (1) H554 b5 Second Heating Circuit Installed without 3 Way Valve and Sensor Mixed Flow Sensor Present (1) / No Mixed Flow sensor Present (0) (E10 Error signal when outside air sensor is not installed.
© MHG Heating Ltd 8.6 Hydraulic Design Single Unit (Option 7) Electrical Connections Single Unit (Option 7) Parameter # H554 b3 Parameters Description Weather Compensation (1) / Constant Flow Temperature Operation (0) H558 b2 Hot Water Storage Sensor (0) / Hot Water Thermostat (1) Default 1 Proposed Change 0 0 1 1 0 (E10 Error signal when outside air sensor is not installed.) (E50 Error signal when sensor is not used.
© MHG Heating Ltd Electrical Connections Single Unit (Option 8) Parameter # H554 b3 Parameters Description Weather Compensation (1) / Constant Flow Temperature Operation (0) Default Proposed Change 1 0 0 1 1 0 (E10 Error signal when outside air sensor is not installed.
© MHG Heating Ltd 8.8 Hydraulic Design Single Unit (Option 9) Electrical Connections Single Unit (Option 9) Parameter # H554 b3 Parameters Description Weather Compensation (1) / Constant Flow Temperature Operation (0) H558 b2 Hot Water Storage Sensor (0) / Hot Water Thermostat (1) Default 1 Proposed Change 0 0 1 1 0 (E10 Error signal when outside air sensor is not installed.) (E50 Error signal when sensor is not used.
© MHG Heating Ltd Electrical Connections Single Unit (Option 10) Boiler Parameter Alterations Parameter # Parameters Description H516 Summer / Winter Automatic Changeover Temperature Default 18 Proposed Change 30 RVA63 Controller Alterations Parameter # Parameters Description 29 Summer / Winter Automatic Changeover Temperature 80 Boiler Control Type LPB/On-Off/Hi-Low 140 LPB Controller / Appliance Communication (Device) 141 LPB Controller / Appliance Communication (Segment) Default 18 2 0 0 Proposed
© MHG Heating Ltd 8.
© MHG Heating Ltd 8.
© MHG Heating Ltd 8.
© MHG Heating Ltd RVA47 Cascade Manager Wiring Terminals.
© MHG Heating Ltd 8.14 Hydraulic Design Single Unit (Option 12) Electrical Connections Single Unit (Option 12) Boiler Mounted Cascade Manager Please refer to System Options 10 and 11 for RVA47 and RVA63 controller wiring information.
© MHG Heating Ltd 9.0 BMS Interface Clip Installation and Parameter Alteration Following the installation of the AGU2.511 communication clip (complete with base mounted wiring connection) onto the front of the LMU64 controller a number of operational parameters within the unit must be altered to ensure the clips operates as required. LMU64 Pictured above with AGU2.511 and OCI420 communication clips.
© MHG Heating Ltd 10.0 Fluing Options Please note that excessive resistance within the flue and combustion air supply systems will lead to a reduction in the output of the appliance and induce operational faults. 16 27 47 75 & 77 4.0 4.0 2.5 1.25 1.0 2.5 1.25 5.0 5.0 4.0 2.0 1.5 4.0 2.0 8.0 8.0 6.0 3.0 2.0 6.0 3.0 16.0 16.0 12.0 6.0 4.0 12.0 6.0 1.00 1.5 2.0 4.5 1.0 2.0 1.5 0.75 0.5 1.5 0.75 0.5 2.5 4.0 3.0 1.5 1.0 3.0 1.5 1.0 4.0 7.0 5.0 2.25 2.0 5.0 2.25 1.75 8.0 15.0 9.0 4.5 3.75 9.0 4.
© MHG Heating Ltd 10.2 Single ProCon Balanced Flued. Vertical Termination. 10.3 Single ProCon Open Flued. Through The Wall Termination. 37 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 10.4 Single ProCon Open Flued. Vertical Termination 10.5 Cascaded Appliance Fluing Installation Open Flued 38 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 10.6 Dimensions of Available Flue Components 39 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 10.7 Balanced Flue Terminal Positions For Boilers Below and Above 70kW Net Input. (All measurements are in mm and are minimum clearances.) Boilers with a rated Input < 70kW Net 300 75 200 Boilers with a rated Input > 70kW Net 600 700 200 200 N/A 150 150 F Terminal Location *Below and opening window etc. Below gutter soil pipes etc. Below Eaves. *Below balconies or car port roof. From vertical drain or soil pipe etc. From internal or external corners.
© MHG Heating Ltd 11.0 Filling The System The Initial filling of a sealed heating system, and subsequent refilling, must be by a method that has been approved by the Water Regulation Advisory Scheme (WRAS) for that type of heating system. i.e.
© MHG Heating Ltd 12.0 System Water Quality Water Treatment, System Cleaning (BS 7592: 2006) The entire primary system MUST be thoroughly cleaned and flushed to remove debris, flux residues, etc. before opening the boiler isolation valves & flooding the boiler. Particular care must be taken where the ProCon boiler is being retro-fitted into an old/existing system, as system silt or magnetite can be very damaging to the new boiler.
© MHG Heating Ltd 13.0 Appliance Controls All appliance operational mode adjustments and settings are undertaken via the unit control fascia Legend Button Label T1 RESET T2 HOT WATER (HWS) T3 MODE T4 HWS SETPOINT T5 HEATING CIRCUIT FLOW TEMPERATURE SETPOINT T6 PROGRAM DOWN T7 PROGRAM UP T8 T9 PROGRAM + PLUS PROGRAM – MINUS T10 INFORMATION Function Resets indicated large flashing fault codes. Places the boiler into fault is no fault is present (E153) Activates HWS generation capability.
© MHG Heating Ltd Legend Button 1 2 Label WATER PRESSURE INDICATOR MAIN DISPLAY 3 COMMISSIONING MODE 4 SPECIFIC OPERATIONAL MODE INDICATOR 5 TIME OF DAY / AUTO RESETTING ERROR 6 HEATING CIRCUIT MODE INDICATOR 7 HOT WATER ACTIVATION INDICATOR Function Not used In ProCon Ranges Flow Temperature or Selected Parameter Setting Commissioning Mode Indicator Full Power (no adjustment.)/Engineers Mode (full adjustment via Program Up & Down Buttons.
© MHG Heating Ltd 13.1 Module Operating Codes 45 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 14.0 Appliance Fault Codes The ProCon range has two levels of fault code indication. Automatic Resetting Fault Code. A small fault code alternating with the time of day. The appliance will stop operating for a limited period/until the error has been corrected. Repeated occurrences of an Automatic Resetting Fault Codes will result in a Manual Reset Fault Code. Manual Reset Fault Code. A large fault code is displayed on the screen along with the symbol.
© MHG Heating Ltd E-60 E-61 E-62 E-77 E-78 E-81 E-82 E-86 E-91 E-92 E-100 E-105 E-110 E-111 E-113 E-117 E-118 E-119 E-124 E-128 E-129 E-130 E-131 E-132 E-133 E-134 E-135 E-140 E-142 E-145 E-146 E-147 E-148 E-150 E-151 E-152 E-153 E-154 E-160 E-161 E-162 E-164 E-166 E-180 E-181 E-183 Faulty Room Sensor Faulty Room Sensor Incorrect Room Unit Connected Air Pressure Sensor Not Detected (Not Used) Water Pressure Sensor Defective (Not Used) LPB Short Circuit (Boiler Cascade Wiring) LPB Address Conflict (Boiler C
© MHG Heating Ltd 14.1 Enhanced Fault Diagnosis Codes (LMU Internal Software Diagnostic Codes) If required a more detailed fault diagnosis code can be viewed. This will assist where a definitive cause for a repeated operational error cannot be found. The enhanced fault diagnosis code is displayed at b0 within the second INFO level. Access to this level is detailed on page 49. The table below indicates a limited number of enhanced fault codes.
© MHG Heating Ltd 15.0 Accessing Boiler Parameters Control Parameter Default Settings. All Units are preset for correct operation. However if alterations are required to enhance the operation of the unit following the application of optional control the procedure is detailed below. The following Pages detail the parameters of the LMU64 controllers, For your assistance the Standard Factory settings are indicated.
© MHG Heating Ltd Level One end User Parameters Line # P1 P2 P5 P10 P11 P12 P13 P14 P15 P16 Description Time of Day Day Of Week Reduced Room Temperature Set Point (If outside air sensor installed) Minimum Boiler Flow Temperature Time Switch 1 Heating Zone 1 Set Points Heating Circuit 1 Time Switch 1 Day Selection Heating Circuit 1 Time Switch 1 First On Heating Circuit 1 Time Switch 1 First Off Heating Circuit 1 Time Switch 1 Second On Heating Circuit 1 Time Switch 1 Second Off Heating Circuit 1 Time Swi
© MHG Heating Ltd Level Two Engineer Parameters # H90 H91 H93 H94 H503 H504 H505 H506 H507 H516 Description Reduced Temperature for DHW DHW Production Control (0=Time control 1=Constant) DHW Production Control 0=Non Eco 1=Eco 75 & 77 HM Range 16 & 27 H (16 & 27 HS) 27 S [47 S] 45,75,77 H 8….60 10 10 10 10 0…1 0 1 0 0 0…1 0 0 0 0 0…1 0 0 0 0 20 ... 90 °C 20 20 20 20 20 ... 90 °C 90 90 90 90 20 ... 90 °C 85 85 85 85 20 ... 90 °C 25 25 25 25 20 ...
© MHG Heating Ltd # Description 27 S [47 S] 45,75,77 H b0=0 b1=0 b2=0 b3=0 b4=1 b5=0 b6=0 b7=0 b0=1 b1=0 b2=0 b3=0 b4=0 b5=0 b6=1 b7=0 b0=0 b1=0 b2=0 b3=0 b4=1 b5=0 b6=0 b7=0 b0=1 b1=0 b2=0 b3=0 b4=0 b5=0 b6=1 b7=0 b0=0 b1=0 b2=0 b3=0 b4=1 b5=0 b6=0 b7=0 b0=1 b1=0 b2=0 b3=0 b4=0 b5=0 b6=1 b7=0 b0=0 b1=0 b2=0 b3=0 b4=1 b5=0 b6=0 b7=0 b0=1 b1=0 b2=0 b3=0 b4=0 b5=0 b6=1 b7=0 30 ... 873 s 150 150 150 150 0 ... 16* 1 1 1 2 {3…12} H555 Setting flags 0 ... 255 H558 Setting flags 0 ...
© MHG Heating Ltd # Description Range 16 & 27 H (16 & 27 HS) 27 S [47 S] 45,75,77 H 75 & 77 HM {Cascade Slave Boilers} H704 2nd Historical Fault – Operating Phase. H705 2nd Historical Fault – Operating Error Code H706 3rd Historical Fault – Number of Occurrences. H707 3rd Historical Fault – Operating Phase. H708 3rd Historical Fault – Operating Error Code H709 4th Historical Fault – Number of Occurrences. H710 4th Historical Fault – Operating Phase.
© MHG Heating Ltd 16.0 RVA47 Cascade Manager (ProCon 75 HM & 77 HM) Legend Button 1 2 3 4 LABEL Function ROOM TEMPERATURE SET POINT ADJUSTER. Assumed Room Temperature if no Room Unit Fitted PROGRAM DOWN & UP BUTTONS Access to Program Settings PROGRAM + PLUS & - MINUS BUTTONS Access to program settings In Sequential Order. DISPLAY SCREEN Operational Status Indicator Automatic Operation 5 MODE SELECTION BUTTONS.
© MHG Heating Ltd 16.1 RVA47 Cascade Manager Settings. The Single and Cascade Master units are preset for correct operation. The following Pages detail the parameters of the RVA47 Cascade Manager and the Standard Factory settings, please note, the installer/commissioning engineer may have changed some of these settings to suit the system installed. There are two levels of access available, as follows.
© MHG Heating Ltd [#] 1 2 3 4 5 6 7 8 9 10 11 13 14 15 16 17 18 19 23 30 31 32 33 34 35 50 51 52 Description End User Level Time of Day Weekday Date Year Day of Week Heating Time Switch 1st On Time Heating Time Switch 1st Off Time Heating Time Switch 2nd On Time Heating Time Switch 2nd Off Time Heating Time Switch 3rd On Time Heating Time Switch 3rd Off Time Required HWS Temperature Heating Night Setback Temperature Frost Protect Temperature Summer/Winter Changeover Temperature Weather Compensation Cu
© MHG Heating Ltd [#] Description Range Defaults 53 56 57 59 60 61 62 66 69 70 71 72 75 76 77 95 100 101 Plant Type Actual System Flow Temperature Actual System Return Temperature Actual System HWS Temperature Attenuated Outside Air Temperature Composite Outside Air Temperature Outside Air Temperature Source Maximum System Flow Temperature Maximum HWS Temperature Nominal Room Temperature Set Point Set Point Of Room Temperature System Flow Temperature Set Point Modules Available in Cascade Lead Module
© MHG Heating Ltd [#] Description Range Defaults 123 HWS Control in Cascade System 0. Controlled Via Master RVA47 Manager 1. Controlled Via All RVA47 Managers in Segment 2. Controlled Via All RVA47 Managers In LPB System HWS Charging Cycles Per 24 Hour Period 0. One Per Day with 2.5 Hour Forward Shift from Heating Time Switch Setting 1. Several Per Day with 1 Hour Forwarding Shifting from Heating Time Switch Setting HWS Temperature Control 0. QAZ21 Sensor 1.
© MHG Heating Ltd [#] Description Range Defaults 147 Central Standby Switching 0. Deactivated 1. Activated Clock Mode 0. Autonomous All Clocks Can Have Different Times 1. System Time Without Adjustment 2. System Time With Adjustment 3. System Clock Master. There Can Only be One Master Auto Time Adjustment Spring Date and Month of Last Sunday in March Auto Time Adjustment Autumn Date and Month of Last Sunday in October Operation of H1 Terminal 0. Changeover of Operation When Volt Free Switch is Made.
© MHG Heating Ltd [#] 2 8 22 30 32 33 35 36 Description OEM Level Maximum Module Temperature When Operating In Manual Mode Pump Run On Time System Heating (HKP) and HWS (SLP) Pumps Minimum System Return Temperature Room Influence Gain Factor Boost Room Temperature Set Point Room Sensor Dependant (QAA10/50/70) Increase. Heat Up Time Reduced Decrease Heat Up Time Increased Frost Protection 0. Frost Protection Program Disabled 1. Frost Protection Program Enabled Heat Gains Increase.
© MHG Heating Ltd 17.0 Commissioning The Appliance 17.1 Pre-Commissioning Checks Prior to undertaking the commissioning of the unit please ensure that the system water has been cleansed and treated with a suitable inhibitor as detailed in Filling the system and system water quality. Prior to applying power to the appliance its circulation pump should be bled and checked to ensure free rotation of the armature. Also ensure that the ignition electrodes spark gap is set to 4mm. 17.
© MHG Heating Ltd The output of the appliance can be altered by using the maximum outout and 0% minimum output. buttons to move between 100% Alterantaivley the output of the appliance can be altered by using the increase the output by 1% per press. buttons to descrease or This mode is maintained until the limit thermostat temperature is reached or the coommissioning buttons are pressed from more than 1 second.
© MHG Heating Ltd The combustion setting required for all ProCon appliances are as detailed in the following table. Gas Type Natural Gas (G20) LPG (G31) High Fire 8.5% C02 11.0% CO2 Low Fire 9.0% CO2 11.0% CO2 17.3 Conversion of the Appliance to Operate on LPG (G31). Unless specified at the time of ordering the appliance/s will be supplied ready to operate on a Natural Gas (G20) fuel supply. The appliances data badge will indicate the type of fuel gas the modules have been set to operate with.
© MHG Heating Ltd 18.0 Routine Inspection and Servicing.(A QAA73 Room Unit/service tool is required to reset the modules service interval timer.) As with all Gas Appliances, we would highly recommended that a competent heating engineer services the ProCon, at least every 12 months. This is assuming a normal daily usage of 8 – 10 hours. If however the boiler is to be operated 24 hours a day, 7 days, we would recommend services every 6 months.
© MHG Heating Ltd h) i) j) k) l) m) n) o) p) q) r) s) If dis-colouration has occurred, then specialist de-scaling of the heat exchanger will be required, however, stress cracking may have occurred, and the heat exchanger may become porous following the de-scale works. If the heat exchanger has not suffered from dis-colouration, as ‘Item g’ above, then a Standard Service can be undertaken. Using a natural bristled brush ONLY, remove the worst of the mineral/debris build up.
© MHG Heating Ltd 20.0 Optional System Controls. If required the following controls can be applied to the ProCon HT range to enhance boiler and system operational efficiency and longevity. (Further detailed guidance can be obtained from the respective controller manuals.) QAA73 Modulating Full Function Room Unit. (Single Boiler Applications Only.) This modulating full function room unit offers the heating user full remote access to the all functions that effect the provision of heat to the respective zone.
© MHG Heating Ltd 21.0 Internal Wiring The internal wiring configurations of the ProCon differ dependant upon the model. H HS S and HM. 21.1 Internal Wiring Diagram 16 , 27 H HS & S 67 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 21.2 Internal Wiring Diagram 47 H & S 68 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 21.3 Internal Wiring Diagram 75 & 77 H 69 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 21.4 Internal Wiring Diagram 75 & 77 HM 70 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 22.0 HM Appliances and Slave units equipped with OCI420 Communication Clips. Communication Operation Indications The RED LED on the OCI420 communication clip mounted on the front of each LMU64 module controller flashes to indicate the detected operational status of the module dictated by the LPB communication from the RVA47 Cascade Manager. LED FLASH STATUS INTERPRETATION OPTIONS LED ON Constantly OCI420 not configured to operate with LMU64 LED OFF Constantly OCI420 Configured.
© MHG Heating Ltd 23.0 Exploded Spares Diagram 16, 27 & 47 72 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 23.0 Exploded Spares Diagram 16, 27 & 47 73 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 23.0 Exploded Spares Diagram 16, 27 & 47 74 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 23.0 Exploded Spares Diagram 16, 27 & 47 75 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 23.0 Exploded Spares Diagram 16, 27 & 47 76 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 23.0 Exploded Spares Diagram 16, 27 & 47 77 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 24.0 Exploded Spares Diagram 75 78 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 24.0 Exploded Spares Diagram 75 79 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd 25.0 Exploded Spares Diagram 77 Exploded diagram To Follow. Please contact our Spares Department. 80 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.
© MHG Heating Ltd Notes 81 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.