Technical data

Procon
. S T 
Typical multiple Procon , ,  &  boiler installation utilizing an RVA Cascade Manager and a RVA
Controller, two heating zones, one of which having mixing valves, and domestic hot water with individual charg-
ing pumps, using a low velocity mixing header. RVA Controller & Housing, an RVA Controller & Housing, 
No QAD/  ow sensors, and OCI Communication Clip-In Modules ( per boiler) required.
Please note;
The Procon,  &  models include an internal pump and therefore an external boiler pumpis
not required.
The wiring of the internal pump on the Procon  MUST be relocated from K (Terminals  &)
to K (Terminals  & )
The boiler pump on the Procon  must be wired to K (Terminals X-)
Essential Boiler Parameter Changes Applicable to System Type .
Line ID Description
Default
Setting
New Setting for
This System
H Summer/Winter Changer Over  
H Hydraulic System Con guration
 { & }
 { & }

H
Boiler Numbering In Cascade
{ = Boiler No,  = Boiler No,  = Boiler No,…  = Boiler
No}
 – 
Fig .a – Hydraulic Layout
Fig .b Wiring Diagram for Models ,  & 
Fig .c Wiring Diagram for Model 
Legend
C &  Heating Zone  &  Temp
Controllers ( Per Zone re-
quired either QAA, QAA
or QAA) or Volt Free En-
able.
OS Outside Air Sensor (QAC)
or 
Ω Resistor {Fitted to
RVA}
SV Safety Valve.
IV Isolation Valve
LSV Lockable Service Valve
S/T Hot Water Sensor (QAZ), or
Volt Free Enable
CWM Cold Water Main
DOC Drain O Cock
NRV Non-Return Valve
RVA Kascade Manager
FS Flow Sensor (QAD/)
RS Return Sensor (QAD/)
ZFS Zone Flow Sensor (QAD)
