The ue terminal of the Procon , , & boilers’ will plume water vapour, heavily and care must be taken
when selecting the terminal position to ensure that a “nuisance situation” is not created.
Where the ue terminal discharges within 2 metres of ground or any upper part of the building where
people have general access, i.e. balcony level, etc., a terminal guard MUST be tted to prevent the terminal
from being touched.
Minimum Distance
All Dimensions are in millimeters, See Fig .
Dimension Description
Minimum
Distance
Dimension Description
Minimum
Distance
A
Directly below an opening,
air brick, window, etc.
J
From an opening, door,
window, etc., in a car port
B
Below gutters, soil pipes,
drain pipes, etc.
K
Vertically from a terminal on
the same wall.
C Below eaves L
Horizontally from a terminal
on the same wall.
D
Below balconies, car port
roof, etc.
M
Above an opening, window,
etc.
E
Vertically from soil pipes,
drain pipes, etc.
N
Horizontally to an opening,
window, etc.
F
From internal or external
corners.
P
Above a level roof (base of
terminal).
G
Above ground, intersecting
roof, balcony level, etc.
Q
Q From adjacent wall (edge
of terminal).
H
From a surface facing the
terminal.
R
From adjacent opening
window.
I
From a terminal facing the
terminal.
S From any other ue terminal.
Note: Dimensions highlighted in BOLD are not recommended locations.
Fig . – Minimum Clearances