Technical data

Procon
. C  F P L
The excess pressure available from the boiler fan for overcoming the frictional resistance of the  ue system is
 Pa. The adjacent table lists the resistances of the  ue components, which will assist the designer in calculat-
ing the resistance of the total  ue system.
As with all vertical  ue systems, thermal up-draught is generated in the vertical sections of a  ue, the graph
below ( g .) shows the Thermal Up-draught generated, in Pas, which can then be deducted from the total
ue resistance.
If the resistance of the total  ue system exceeds  Pa’s, this will result in a reduction of the boiler output.
The graph below ( g .) shows the available maximum boiler output in relation to  ue resistance.
15H 25H 45H 75H
Concentric Flue Components
Standard Wall Terminal . . . .
Vertical Discharge Wall Terminal . . . .
Vertical Terminal . . . .
 mm Flue Extension . . . .
 mm Flue Extension . . . .
° Bend . . . .
° Bend . . . .
 mm PPS Flue Components
Concentric to Twin Pipe Adapter . . . .
Exhaust Pipe Terminal . . . .
Air Pipe Terminal . . . .
 mm Flue Extension . . . .
 mm Flue Extension . . . .
° Bend . . . .
° Bend . . . .
ermal Up-draught Graph Boiler Output / Flue Resistance Graph
Fig .a Thermal Up-draught when  ue gas
temperature ºC and outside temperature -° C.
A = Flue insulated or within the building.
B = Flue un-insulated and exterior to the
building.
Fig .b – E ect of the  ue system
resistance on the boiler output.
