User guide

Data Sheet
4LSL
Loudspeaker Function Card
Commissioning Functions
The 4LSL measuring module includes additional commissioning and servicing
aids to better control the measurement equipment or the loudspeaker circuits.
These are:
- Switchable drive display (VU meter) to check precisely all signals to be meas-
ured
- Display of the most important functions on the front plate
- Automatic or manual calibration of loudspeaker circuits
- Diverse group and individual messages
- PC-based configuration
- Measurement data transmission to the DVS-21 central system
- Simulation of all processes which the module has
Summary of the Functions
- Precision measuring for impedance error detection: 1-100% in 1% steps
(% of installed loudspeaker load)
- Number of independent loudspeaker circuits or measurement channels:
4
- Measurement channels can be individually switched on/off
- Loudspeaker minimum/maximum load per channel: 2.5 Watt / 150 Watt
- Loudspeaker load check during commissioning
- Manually or automatically configurable impedance deviation limits
- Verification of impedance deviation through automatic multiple subsequent
measurements
- Automatic or manual measuring procedure
- Checking of the test signal generator before each measurement
- Wire breakage or short circuit detection
- Allocation of an occurring earth leakage to a loudspeaker circuit (earth leak-
age detection through TG01)
- Transfer of all measurement data to the DVS-21 central system
- Display of all statuses by LEDs on the front plate
- Loudspeaker circuit relays: 4 (1/channel)
- Generation of positive and negative public address acknowledgements
- Programmable night-reduction function for public address acknowledgement
- Configurable amplifier protection function for loudspeaker circuit short circuit
- Making possible public address in the case of a short circuit (group public
address)
- Diverse group and individual messages
- Full control over all procedures through the DVS-21 central system
- PC-based configuration
- Commissioning and service aids on-board
Further details can be found in the commissioning instructions.
Date:
13.03.2009
Page:
6/7
Author:
HS
Document-No.:
DB_4LSL_2830_01
© 2008 ProCom, All rights and technical changes reserved