SPECIFICATIONS
VENTILATION
Example: A 220,000 Btu/Hr (64.5 kw) heater
requires one of the following:
• a two-car garage door [16 feet (4.88 meter)
opening] raised 5" (12.7 cm)
• a single-car garage door [9 feet (2.74 me-
ter) opening] raised 9" (22.9 cm)
• two, 30" (76.2 cm) windows raised 16"
(40.6 cm)
FUELS
• noticeable odor
• additional fuel lter maintenance
* Use of #2 diesel/fuel oil in extreme cold
temperatures may require nontoxic anti-icer
additives.
Do not use fuels heavier than No. 2 grade
or heavy oils such as oil drained from crank-
cases. These heavy oils will not ignite properly
and will contaminate the heater.
IMPORTANT: Use a KEROSENE ONLY (blue)
or DIESEL ONLY (yellow) storage container.
Be sure storage container is clean. Foreign
matter such as rust, dirt or water will cause the
ignition control assembly to shut down heater.
Foreign matter may also require heater's fuel
system to be frequently cleaned.
PCK110VT PCK160VT PCK175VT PCK220VT
Output Rating 80K-110K 110K-160K 125K-175K 160K-220K
Fuel (all models) Use only kerosene, #1/#2 diesel*/fuel oil, JET A or JP-8 fuels
Fuel Tank Capacity 5.5 gal/20.8 L 10 gal/37.9 L 10 gal/37.9 L 14 gal/53 L
Fuel Consumption (per hr) 0.82 gal/3.1 L 1.19 gal/4.5 L 1.3 gal/4.9 L 1.64 gal/6.2 L
Pump Pressure 6.9 PSI (hot) 6.7 PSI (hot) 6.8 PSI (hot) 8.4 PSI (hot)
Electric Requirements 120 V/60 HZ 120 V/60 HZ 120 V/60 HZ 120 V/60 HZ
Amperage (Normal Run) 2.9 3.2 3.4 4.6
Typical Motor Speed 3400 RPM 3400 RPM 3400 RPM 3400 RPM
Motor 1/4 hp 1/4 hp 1/4 hp 1/4 hp
Shipping Weight 42 lbs/19 kg 71 lbs/32.2 kg 71 lbs/32.2 kg 77 lbs/35 kg
Heater Weight without
Fuel (approx)
36 lbs/16.3 kg
60.5 lbs/27.4 kg 60.5 lbs/27.4 kg 66 lbs/29.9 kg
WARNING: Use only kero-
sene, #1/#2 diesel/fuel oil, JET
A or JP-8 fuels to avoid risk
of re or explosion. Never use
gasoline, oil drained from crank-
cases, naphtha, paint thinners,
alcohol or other highly am-
mable fuels.
Use only kerosene, #1/#2 diesel*/fuel oil,
JET A, JP-8 fuels. Heavier fuels such as No.
2 fuel oil, No. 2 diesel fuel may also be used
but will result in:
WARNING: Provide a fresh air
opening of at least three square
feet (2,800 square cm) for each
100,000 BTU/HR rating. Provide
extra fresh air if more heaters
are being used. The minimum
ventilation requirements must
be followed to avoid risks as-
sociated with carbon monoxide
poisoning. Make certain these
requirements are met prior to
operating heater.