TROUBLESHOOTING
DISPLAY POSSIBLE CAUSE REMEDY
Display shows C7 Control
button stuck.
1. One or more of the control
buttons is depressed continu-
ously (stuck).
2. Defective control assembly.
1. Unplug heater. Depress and
release each control button
several times to check opera-
tion. Every button should click
every time it is depressed.
2. Replace control assembly.
Display shows C8 Te m -
perature Over 100°F.
1. Room or ambient tempera-
ture exceeds 100°F.
1. Operate heater in a cooler
environment.
Display shows C9 Low
Pressure (Setting 5).
1. Air line or tting leaking.
2. Pump cover leaking. Pump
cover screws loose.
3. Pump cover gasket leaking.
Pump output lter clogged.
4. Pump pressure is low.
5. Pump pressure is low. Can-
not adjust to specification.
Pump lters are dirty.
6. Pump pressure is low, pump
has excessive wear or im-
proper adjustment.
1. Unplug heater. Check air
lines and fittings of leaks.
Correct all leaks.
2. Unplug heater. Check pump
cover for leaks. Tighten pump
cover screws to 10-20 in-lbs.
3. Unplug heater Replace pump
output lter. See Pump Rotor,
page 17.
4. Adjust pump pressure to
specication. See Pump Pres-
sure Adjustment, page 14.
5. Replace pump filters. See
page 13.
6. Adjust pump rotor gap or re-
place pump rotor and blades.
See page 17.
WARNING: High voltage! Unplug heater before servicing.
FAULT CONDITION
(Continued) Heater ignites but control assembly shuts heater off before
running out of fuel.