Instruction manual

OPERATIONS for E5CK (Continued):
Mode Parameter Settings:
The Omron E5CK temperature controller has been programmed prior to shipment, so
no additional programming is normally necessary. The table below shows the various
controller settings for this unit when properly configured to operate the TYTAN inline
heater. Some internal menus have been factory programmed and subsequently locked.
Those menus are not listed.
The selections in bold indicate settings that have been changed from the original
factory default for operation with the TYTAN inline heater.
Mode Parameter Description Setting
SP-n Set point during ramp NP
O Manipulated variable (MV) monitor for
heat
0
C-o Manipulated variable (MV) monitor for
cool
NP
Level 0
r – S Run/Stop Run
A t Auto Tune (AT) execute/cancel o-FF
SP-0 Set point 0 (Process Set point) Determined by Operator
A L – 1 High Alarm 120°C (248°F)
A L – 2 Temperature Deviation 10°C (15°F)
P Proportional Band 10.0 (default)**
i Integral Time 233 (default)**
D Derivative Time 40 (default)**
C-SC Cooling coefficient
C-db Dead band
Of-R Manual reset value
HYS Hysteresis (heat)
CHYS Hysteresis (cool)
C P Heating control period/cycle time 1sec
C-CP Cooling control period/cycle time
Level 1
S P r U Set Point ramp time unit M, minutes
** The P, I and D values may change following the execution of Auto-tune.
Table 7: Omron E5CK Parameters
M-45-02 TYTAN Manual
Revision - Date: 01 – 11/16/07
35