Installation manual
CM-02-001
TYTANu DI Water Heater
O.I. 6/27/03 Installation, Operation and Maintenance Manual
ECO page 14
4.1.3 Mode Parameter Settings:
Omron E5CK temperature controller: When in the selected mode press the Display Key for less than one second to switch
parameters.
Mode Parameter
Description Setting
Level 0 r – S Run/Stop Run
A t Auto Tune (AT) execute/cancel O-FF
A L – 1 High Alarm 120°C
A L – 2 Temperature Deviation 110°C
P Proportional Band 10.0 (default)
i Integral Time 233 (default)
D Derivative Time 40 (default)
Level 1
C P Heating Control Period/Cycle Time 1sec
S P r U Set Point ramp time unit M, minutes
S P r t Set Point ramp set value 0
mU – S Sets Manipulated Variable (MV) when operation
stop
0.0%
mU – E Sets MV when an input error occurs 0.0%
O L – H MV upper limit 105.0%
O L – L MV lower limit 0.0%
O r L Max. allowed change width of MV / change rate
limit
0.0%/sec (= disabled)
i n F Input digital filter constant 0 sec
A L H 1 Alarm 1 hysteresis 1.00%
A L H 2 Alarm 2 hysteresis 1.00%
A L H 3 Alarm 3 hysteresis 0.01%
i n S H Input shift upper limit temperature Factory Calibrated
Level 2
i n S L Input shift lower limit temperature Factory Calibrated