Modbus to Analog Configuration
After opening communication, use the following steps to change the Control Mode from
Modbus operation to Analog operation:
1. FLOW-BUS tab > Test Flow-BUS and DDE
a. Or Press F6
2. Select the following parameters to view simultaneously
a. Parameter 7 –
InitReset
b. Parameter 12 –
IO Status
3. Set parameter
InitReset to 64 (unlocked)
4. Read parameter
IO Status
5. Add 64 from the read value
a. New Parameter Value: 79
6. Write the new value to parameter
IO Status
7. Set parameter
InitReset to 82 (locked)
8. Restart Bronkhorst instrument
a. InitReset must be unlocked/locked for the new Control Mode to remain after the