Operating instructions

3 Temperature Sensor Type and Temperature Range
Input Temperature Sensor Type Register Value LED Display Temperature Range
Platinum resistance (Pt100) type3 15
0.0 to 100.0
o
C
Platinum resistance (Pt100) type2 14
-20.0 to 500.0
o
C
Platinum resistance (Pt100) type1 13
-200 to 600
o
C
Platinum resistance (JPt100) type2 12
0.0 to 100.0
o
C
Platinum resistance (JPt100) type1 11
-20.0 to 400.0
o
C
Thermocouple (TC) B type 10
100 to 1800
o
C
Thermocouple (TC) S type 9
0 to 1700
o
C
Thermocouple (TC) R type 8
0 to 1700
o
C
Thermocouple (TC) N type 7
-200 to 1300
o
C
Thermocouple (TC) E type 6
0 to 600
o
C
Thermocouple (TC) T type2 5
-20.0 to 400.0
o
C
Thermocouple (TC) T type1 4
-200 to 400
o
C
Thermocouple (TC) J type2 3
-20.0 to 400.0
o
C
Thermocouple (TC) J type1 2
-100 to 850
o
C
Thermocouple (TC) K type2 1
-20.0 to 500.0
o
C
Thermocouple (TC) K type1 0
-200 to 1300
o
C
Thermocouple (TC) L type 16
-200 to 850
o
C
Thermocouple (TC) U type 17
-200 to 500
o
C
Thermocouple (TC) Txk type 18
-200 to 800
o
C
4 Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, the controller will default to the
operation mode. Press the
key to switch to regulation mode. If the key is pressed for more than 3 seconds, the controller will
switch to the initial setting mode. Pressing the key while in the regulation mode or initial setting mode, forces the controller to return
to the operation mode. PV/SV : Sets the temperature set point and displays the temperature process value. Use the and keys to
set the temperature set point.
Setting method: While in any function mode, press the key to select the desired function and use the and keys to change
settings. Press
key to save the changes. Menu items are listed below.
Regulation Mode
Operation Mode
Initial Setting Mode
Set input type
Use key to
set temperature set point
Auto-tuning
(Set in PID control and RUN mode)
Press
Press
Press
Set proportional band (Kp)
(in PID control)
Press
Set temperature unit
do not display when analog input
Press
Control setting RUN or STOP
Press
Set integral time (Ki)
(in PID control)
Press
Set upper-limit of
temperature range
Upper-limit alarm 1
(This parameter is available only when
ALA1 function enables)
Press
Press
Set derivative time (Kt)
(in PID control)
Press
Set lower-limit of
temperature range
Lower-limit alarm 1
(This parameter is available only when
ALA1 function enables)
Press
Press
or P/PD control offset (when
PID control is ON and Ki=0 set the value of
PdoF. If Ki0, AT (auto-tuning, will
automatically set the value of ioF.
Press
Upper-limit alarm 2
(This parameter is available only when
ALA2 function enables)
Press
Sets Control Method: on/off, PID, or
manual.
or Heating/Cooling hysteresis.
(in ON/OFF control)
Press
Lower-limit alarm 2
(This parameter is available only when
ALA2 function enables)
Press
Select heating or cooling control.
Press