Operating instructions

3. Initial Setting Mode: Initial settings of the controller and communication parameters
LED Ex
lanation Default
INPUT: Select input temperature sensor type
(Please refer to the contents of the “Temperature Sensor Type and Temperature Range” for detail)
PT2
Engineering Unit(°F or °C): Select engineering unit F or C.
o
C
T-High: Upper limit for temperature range. 500.0
T-Low: Lower limit for temperature range. -20.0
CONTROL METHOD (ON/OFF, PID, or manual tuning [
]): Sets the control method for the set
point value.
PID
Control Action (Direct or Reverse Acting): Cooling [Cool] or heating [HEAT]. HEAT
ALARM 1: Alarm 1 setting. (See Alarm Output Section for set values and descriptions). 0
ALARM 2: Alarm 2 setting. (See Alarm Output Section for set values and descriptions).
0
C WE: Write-in function disabled/enabled. Can be set only when unit is equipped with serial
communication.
OFF
C NO: Address setting. Can be set only when unit is equipped with serial communication.
1
BPS: Baud rate setting. Can be set only when unit is equipped with serial communication.
9600
Length: Data length setting. Can be set only when unit is equipped with serial communication.
7
Parity: Parity bit setting. Can be set only when unit is equipped with serial communication.
E
Stop Bit: Stop bit setting. Can be set only when unit is equipped with serial communication.
1
Execution :
The programming execution is initiated through in the operation mode.
When
is set to , the program will start to execute in order from the step 0 of the start pattern.
When
is set to , the program will stop and the control output is disabled
5 Heating and Cooling
Temperature control can be achieved either by heating or cooling. Please refer to the following for the operation: Settings for heat or
cool operation are found in the initial settings mode under .
Select
, for heating (reverse) control on Output 1.
Select
, for cooling (forward) control on Output 1
Input Error Indication
Setting
value
Temperature sensor is not connected
Measured temperature value exceeds
the temperature range
Unknown input
PV
SV
6 Alarm Outputs
Depending on the controller model, there can be up to two alarm outputs. Each alarm output can be configured for an alarm type
listed below. Alarm types are set in the initial setting mode. The alarm output is activated whenever the process temperature value
(PV) is getting higher or lower than the set point of alarm limit.
Set
Value
Alarm Type Alarm Output Operation
0 Alarm function disabled Out
p
ut OFF
1
Deviation upper- and lower-limit:
This alarm output operates when PV value is higher than the setting value
SV+(AL-H) or lower than the setting value SV-(AL-L).
ON
OFF
SV-(AL-L)
SV
SV+(AL-H)
2
Deviation upper-limit:
This alarm output operates when PV value is higher than the setting value
SV+(AL-H).
ON
OFF
SV
SV+(AL-H)
3
Deviation lower-limit:
This alarm output operates when PV value is lower than the setting value
SV-(AL-L).
ON
OFF
SV
SV-(AL-L)
4
Reverse deviation upper- and lower-limit:
This alarm output operates when PV value is in the range of the setting value
SV+(AL-H) and SV-(AL-L).
ON
OFF
SV
SV-(AL-L)
SV+(AL-H)