Install Instructions

7
TECHNICIAN SETUP MENU
The second stage will turn on at 2x the swing setting. The second stage will turn off when 1x the
swing is reached. For example, if the swing setting is .8 degrees for heating and the thermostat is
set at 70ºF, the first stage will turn on at approximately 69.2ºF. The second stage will turn on at
68.4ºF. The second stage will turn off at 69.2ºF and the first will turn off at 70.8ºF.
PRO1 Tip
Technician Setup Menu
This thermostat has a technician setup menu
for easy installer configuration. To set up the
thermostat for your particular application:
Configure the installer options as
desired using the table below.
Use the or keys to
change settings and the NEXT STEP
or PREV STEP key to move from one
option to another. Note: Only press
DONE key when you want to exit the
Technician Setup options.
Press MENU button
Press and hold TECH SET button for 3
seconds. This 3 second delay is
designed so that homeowners do not
accidentally access the installer settings.
1.
2.
3.
This feature will flash
“FILT” in the display
after the elapsed run
time to remind the
user to change the
filter. A setting of
“off” will disable this
feature.
This feature allows
the installer to
change the
calibration of the
room temperature
display. For
example, if the
thermostat reads 70°
and you would like it
to read 72° then
select +2.
The swing setting,
often called “cycle
rate”, “differential”
or “anticipation” is
adjustable. A smaller
swing setting will
cause more frequent
cycles and a larger
swing setting will
cause fewer cycles.
The swing setting,
often called “cycle
rate”, “differential”
or “anticipation” is
adjustable. A
smaller swing setting
will cause more
frequent cycles and a
larger swing setting
will cause fewer
cycles.
The heating swing
setting is adjustable
from ±0.4°F to
±2°F. For example:
A swing setting of
0.5°F will turn the
heating on at
approximately 0.5°F
below the setpoint
and turn the heating
off at approximately
0.5°F above the
setpoint.
The cooling swing
setting is adjustable
from ±0.4°F to
±2°F. For example:
A swing setting of
0.5°F will turn the
cooling on at
approximately 0.5°F
above the setpoint
and turn the cooling
off at approximately
0.5°F below the
setpoint.
Selecting “ON” will
not allow the
compressor to be
turned on for 5
minutes after the last
time the compressor
was on. Select “off
to remove this delay.
You can select the
minimum compressor
run time from “off”,
“3”, “4”, or “5”
minutes. If 3, 4, or 5
is selected, the
compressor will run
for at least the
selected time before
turning off.
You can adjust the
room temperature
display to ready -4°F
to +4°F above or
below the factory
calibrated reading.
You can adjust the
filter change
reminder from “off
to 2000 hours of
runtime in 50 hour
increments.
Feature
Description
Adjustment
Options
LCD Will Show
Factory
Default Settings
Off 0 ºF Off On 0.5 ºF 0.4 ºF
This feature allows
the installer to select
the minimum run
time for the
compressor. For
example: A setting of
4 will force the
compressor to run for
at least 4 minutes
every time the
compressor turns on,
regardless of the
room temperature.
Minimum
Compressor
On Time
Compressor
Short Cycle
Delay
Cooling
Swing
Heating
Swing
Room
Temperature
Calibration
Filter
Change
Reminder
Feature
The compressor short
cycle delay protects the
compressor from “short
cycling”. This feature
will not allow the
compressor to be turned
on for 5 minutes after it
was last turned off.