10 | Sump Pump Control System
TEST and CALIBRATION
1. Allow water to ll the sump pit up to the LevelGuard’s Switch “ON Point
2. Sump pump will turn on within 3 seconds of the water level reaching the switch
point and start its Sump Self-Calibration
3. The pump will remain on for 13 seconds or until the water level drops below the
Lower Switch Point
4. If the Lower Switch Point is not reached during this cycle the LevelGuard will increase
the pump run time by 1 second on each subsequent cycle until the Lower Switch
Point is reached or until the total pump run time is 60 seconds.
5. The LevelGuard then calculates the Maximum Pump Run-time. It will use this time
calculation to prevent pump run-on.
Electrical Connection-01
“SWITCH OFF” When Water
is Pumped Down to
3” Below Bottom
“SWITCH ON”
When Water Reaches Top
GFCI
Protected
Outlet
Red and/or Blue wire – connect to pump Black wire
4. Follow state and local electrical codes for ALL connections!
5. Proceed to “TEST section.