Specifications

Minitrend
®
GR 7
Firmware Credit System
The credits system is a flexible way of adding to the recorder features without having to upgrade the firmware. Simply
purchase a number of credits to cover your current and possible future requirements and the recorder will be delivered with
the credits loaded.
Credits can be applied as desired to the Firmware functions until the total number of credits purchased has been used up.
Additional credits can be purchased later if new features are to be activated and not enough credits are available to support
these additional functions.
Firmware options are selected using the Model Selection Guide. Details of each firmware option are listed here.
Firmware
option
Credit
value
Description
Full Maths 4 Full (Block) Math - this can handle math expressions that can consist of expressions up to 100-
characters in length. (Note 1)
Full Maths with
Scripting
6 A powerful multi-line scripting ability available to solve complex state based applications. Eg.: “If
.. X happens, then Y will happen, else.. Z will occur. (Note 1)
Fast Scanning
mode
5 For fast processes, the scan rate and recording of the data can be set for up to 50 times per
second (20ms) for up to 8 inputs.
Totalisers/
Sterilisation
calculation
4 Each pen can be associated with a totaliser. Using extra pens, the totalised values can be dis-
played and recorded; multiple totals can be calculated out of the same variable (weekly,
monthly, etc.). The totaliser function can handle Fo and Po sterilisation calculation. (Note 1&4 )
Custom Screens
4 Import custom built screens that have been created in GR Series Screen Designer. (Note 2)
Reports 3 Generate reports manually or using the event system to show daily/weekly/monthly Totals, Max/
Mins, Averages, Current Value. Messages, Message Lists - Alarm, System, Diagnostic, Security
& User, Counters, Digital Inputs, and Digital Outputs. Reports can be printed, e-mailed as an
attachment or exported to external media in RTF format. Also batch report format to support
batch operation.
Events 6 Events are certain conditions or operations that can be set up and logged according to the time
and date of an occurrence. Subsequently events can be reviewed or displayed on a graph.
The Event Causes include:
Alarms - Into/Out of and Alarm Ack Totals -
Start/Stop/Reset/Reset and Start Digital Input
- ON/OFF/State Change T/C Burnout
Scheduled - Once/Interval/Specific Days/
Month End User Counters
Max/Mins - Reset
System - Power ON/Setup Change/ Internal
Memory Low/Export Memory Low/ FTP
Memory Low
User Action - Mark Chart,
Batch - Start/Stop/Pause.
TUS - Start/Stop
AMS2750 Timer -TC Timers/Process Timers
TC Health Monitor
The Event Effects include:
Mark Chart –User Defined/Preset Logging
Start/Stop
Totaliser – Start/Stop/Reset/Reset & Start,
Digital Output – ON/OFF
Alarm Acknowledge Emails, Screen
Change, Print Screen, Counters
Reset/Increment
Max/Min (Reset)
Chart Control - Pause/Stop/Resume/
Clear/Prefill
Clear All Messages, Delayed Event Script
Timers – Start/Stop/Reset/Reset & Start Play
Sound – Start/Stop
Display Alert, Reports
Batch – Start/Stop/Pause
Update Tabular Readings
Each event marker can be recorded for analysis using the Trend Manager Pro Software Suite.
(Note 2)
Health Watch/
Maintenance
2 The recorder keeps track of important “life actions” for improved diagnostics and preventative
maintenance notification. Including Powered On, Last powered On, Time On since power up,
Total On time, Total Off time, Longest Off time, Lithium cell life, Backlight life left at 100% bright-
ness, Compact Flash insertions, Hi/Lo CJC value (Hi & Lo temps), Analogue In last factory/user
cal, Relay operations.