Specifications

Minitrend
®
GR 13
Specification Design Attributes
Cold Junction
Compensation
Internal compensation with the ability to manually adjust values, External Input for
compensation, External CJC value specified
Input Resolution 0.0015% (16 Bit ADC)
Input Impedance Current loop resistance: 10 ohms, use ±0.1% external resistor. Volts >1M, all other 10M
Source Impedance T/C and RTD: 100 ohms per lead maximum. (A single point cal on Slot A will improve
accuracy for a lead resistance above 10 ohms).
Square Root Extraction Available as standard on every input type
Sensor Compensation Single point and Dual point
Input Sampling Rate Recorder has 2 available slots with up to 8 analog inputs each; the input sampling rate is
dependent on actuation type.
All Inputs: 100mS (10Hz), 200mS (5Hz), 500mS (2Hz)
Fast Sampling: 20mS (50Hz) - mA, mV, Volts and Ohms only
Scales, Linear &
Logarithmic
Normal and Scientific notation
Decimal Point automatic or programmable
Engineering units, user definable (10 characters)
Logarithmic Decade limits: -38 min, to +38 max, (recommend up to 20 decades on one
screen to ensure clarity)
Input Isolation 300VAC channel-to-channel, channel-to-ground
Noise Rejection
(at 50/60Hz) +/-2%
Common mode: 2Hz = -120dB, 5Hz = -120dB, 10Hz = -120dB
Normal Mode: 2Hz = -85dB, 5Hz = -80dB, 10Hz = -48dB
Specification Logging
Logging Method Sample, Average, Min/Max - can be set independently per pen
Logging Types Continuous, Fuzzy
Logging Rate From 20 msec. to 60 hours per pen
Fuzzy Logging A secure data storage technique which delivers data compression ratio of 100:1 or more;
self teaching, storing the data at a variable rate to match the process
Specifications Physical Parameters
Enclosure/Bezel Zinc plated steel case with high impact resistant polycarbonate bezel; scratch resistant
lens. NEMA 3 / IP55 protection rating standard. Optional NEMA 4X / IP66 (Front face only)
Mounting Panel Unlimited mounting angle. For the best view of the display the viewing angle should not
exceed 55° from the left or right, 40° looking down and 50° looking up at the recorder
display. Mounting adjustable for panel thickness of 2mm to 20mm. Adapter kits available
for covering existing panel cutouts.
Dimensions W: 144mm (5.67”), H: 144mm (5.67”), D: 200mm (7.87”). Additional 80mm (3.15”)
clearance recommended for a straight type power cable and signal connectors. Cutout 138
x 138mm (5.43 x 5.43”)
Weight 2.7 Kg (6lb) max.
Colour Bezel: Black or Grey
Wiring Connections IEC Power Plug. Removable terminal strip for input and alarm connections